13-10 Comparator Operand
Array [4]
Option:
Function:
[68]
Below I low
[69]
Above I high
[70]
Out of speed range
[71]
Below speed low
[72]
Above speed high
[75]
Out of feedb. range
[76]
Below feedb. low
[77]
Above feedb. high
[80]
Thermal warning
[82]
Mains out of range
[85]
Warning
[86]
Alarm (trip)
[87]
Alarm (trip lock)
[90]
Bus OK
[91]
Torque limit & stop
[92]
Brake fault (IGBT)
[93]
Mech. brake control
[94]
Safe stop active
[100] Comparator 0
[101] Comparator 1
[102] Comparator 2
[103] Comparator 3
[104] Comparator 4
[105] Comparator 5
[110] Logic rule 0
[111] Logic rule 1
[112] Logic rule 2
[113] Logic rule 3
[114] Logic rule 4
[115] Logic rule 5
[120] SL Time-out 0
[121] SL Time-out 1
[122] SL Time-out 2
[123] SL Time-out 3
[124] SL Time-out 4
[125] SL Time-out 5
[126] SL Time-out 6
[127] SL Time-out 7
[130] Digital input DI18
[131] Digital input DI19
[132] Digital input DI27
[133] Digital input DI29
[134] Digital input DI32
[135] Digital input DI33
[150] SL digital output A
[151] SL digital output B
[152] SL digital output C
[153] SL digital output D
[154] SL digital output E
[155] SL digital output F
[160] Relay 1
13-10 Comparator Operand
Array [4]
Option:
Function:
[161] Relay 2
[180] Local ref. active
[181] Remote ref. active
[182] Start command
[183] Drive stopped
[185] Drive in hand mode
[186] Drive in auto mode
[187] Start command
given
[190] Digital input x30 2
[191] Digital input x30 3
[192] Digital input x30 4
13-11 Comparator Operator
Array [6]
Option:
Function:
[0]
*
<
Select < [0] for the result of the evaluation
to be TRUE, when the variable selected in
is smaller than
the fixed value in
.
The result will be FALSE, if the variable
selected in
is
greater than the fixed value in
.
[1]
≈ (equal)
Select ≈ [1] for the result of the evaluation
to be TRUE, when the variable selected in
is approximately
equal to the fixed value in
[2]
>
Select > [2] for the inverse logic of option <
[0].
[5]
TRUE longer
than..
[6]
FALSE longer
than..
[7]
TRUE shorter
than..
[8]
FALSE
shorter
than..
13-12 Comparator Value
Array [6]
Range:
Function:
Size related
*
[-100000.000 -
100000.000 ]
Enter the ‘trigger level’ for the
variable that is monitored by
this comparator. This is an
array parameter containing
comparator values 0 to 5.
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CC.02 - VLT
®
is a registered Danfoss trademark
101