The Bottom section (c) always shows the state of the
frequency converter in Status mode.
It is possible to toggle between three status read-out
displays by pressing the [Status] key.
Operating variables with different formatting are shown in
each status screen - see below.
Several values or measurements can be linked to each of
the displayed operating variables. The values /
measurements to be displayed can be defined via
0-21 Display Line 1.2 Small
,
0-22 Display Line 1.3 Small
,
0-23 Display Line 2 Large
and
0-24 Display Line 3 Large
, which can be accessed via [QUICK
MENU], "Q3 Function Setups", "Q3-1 General Settings",
"Q3-13 Display Settings".
Each value/measurement readout parameter selected in
to
0-24 Display Line 3 Large
has
its own scale and number of digits after a possible decimal
point. Larger numeric values are displayed with few digits
after the decimal point.
Ex.: Current readout
5.25 A; 15.2 A 105 A.
Status display I:
This read-out state is standard after start-up or initiali-
sation.
Use [INFO] to obtain information about the value/
measurement linked to the displayed operating variables
(1.1, 1.2, 1.3, 2, and 3).
See the operating variables shown in the display in this
illustration. 1.1, 1.2 and 1.3 are shown in small size. 2 and
3 are shown in medium size.
1.1
2
3
1.3
1.2
130BP041.10
799 RPM
Auto Remote Ramping
1 (1)
36.4 kw
7.83 A
0.000
53.2 %
Status
Status display II:
See the operating variables (1.1, 1.2, 1.3, and 2) shown in
the display in this illustration.
In the example, Speed, Motor current, Motor power and
Frequency are selected as variables in the first and second
lines.
1.1, 1.2 and 1.3 are shown in small size. 2 is shown in large
size.
1.1
1.2
2
1.3
130BP062.10
207RPM
Auto Remote Running
1 (1)
24.4 kW
5.25A
6.9
Hz
Status
Status display III:
This state displays the event and action of the Smart Logic
Control. For further information, see
.
130BP063.10
778 RPM
Auto Remote Running
1 (1)
4.0 kW
0.86 A
State: 0 off 0 (off)
When: -
Do: -
Status
Display Contrast Adjustment
Press [status] and [
▲
] for darker display
Press [status] and [
▼
] for brighter display
Top section
Middle section
Bottom section
Status
43 RPM
1.4 Hz
Auto Remote Running
! Pwr.card temp (W29)
2.9%
5.44 A
25.3kW
1(1)
130BP074.10
!
How to Programme
VLT
®
HVAC Drive Programming Guide
10
MG.11.CC.02 - VLT
®
is a registered Danfoss trademark