5-19 Terminal 37 Safe Stop
Option:
Function:
[7]
PTC 1 &
Relay W
This choice is used when the PTC option is
gated together with a Stop button through a
Safety relay to T-37. Coasts frequency
converter when safe stop is activated (T-37
off). When safe stop circuit is reestablished,
the frequency converter will continue without
manual reset, unless a Digital Input set to
PTC Card 1 [80] is (still) enabled. Choice 7 is
only available when the MCB 112 PTC
Thermistor Card is connected.
[8]
PTC 1 &
Relay A/W
This choice makes it possible to use a
combination of Alarm and Warning. Choice 8
is only available when the MCB 112 PTC
Thermistor Card is connected.
[9]
PTC 1 &
Relay W/A
This choice makes it possible to use a
combination of Alarm and Warning. Choice 9
is only available when the MCB 112 PTC
Thermistor Card is connected.
Choises 4 - 9 are only available when the MCB 112 PTC
Thermistor Card is connected.
NOTE
When Auto Reset/Warning is selected the frequency
converter opens up for automatic restart.
Overview of functions, alarms and warnings
Function
No.
PTC
Relay
No Function
[0]
-
-
Safe Stop Alarm
[1]*
-
Safe Stop [A68]
Safe Stop Warning
[3]
-
Safe Stop [W68]
PTC 1 Alarm
[4]
PTC 1 Safe Stop
[A71]
-
PTC 1 Warning
[5]
PTC 1 Safe Stop
[W71]
-
PTC 1 & Relay A
[6]
PTC 1 Safe Stop
[A71]
Safe Stop [A68]
PTC 1 & Relay W
[7]
PTC 1 Safe Stop
[W71]
Safe Stop [W68]
PTC 1 & Relay A/W [8]
PTC 1 Safe Stop
[A71]
Safe Stop [W68]
PTC 1 & Relay W/A [9]
PTC 1 Safe Stop
[W71]
Safe Stop [A68]
W means warning and A means alarm. For further information, see
Alarms and Warnings in section Troubleshooting in the Design Guide
or the Operating Instructions
A dangerous failure related to Safe Stop will give Alarm:
Dangerous Failure [A72].
Please refer to
in
.
3.7.4 5-3* Digital Outputs
Parameters for configuring the output functions for the
output terminals. The 2 solid-state digital outputs are
common for terminals 27 and 29. Set the I/O function for
terminal 27 in
and set the I/O
function for terminal 29 in
. These
parameters cannot be adjusted while the motor is running.
The digital outputs can be programmed
with these functions:
[0]
No operation
Default for all digital outputs and relay
outputs
[1]
Control ready The control board receives supply voltage.
[2]
Drive ready
The frequency converter is ready for
operation and applies a supply signal on
the control board.
[3]
Drive ready /
remote
control
The frequency converter is ready for
operation and is in Auto On mode.
[4]
Stand-by / no
warning
The frequency converter is ready for
operation. No start or stop command is
been given (start/disable). There are no
warnings.
[5]
Running
The motor is running.
[6]
Running / no
warning
The output speed is higher than the speed
set in
1-81 Min Speed for Function at Stop
. The motor is running and there are
no warnings.
[8]
Run on
reference / no
warning
The motor runs at reference speed.
[9]
Alarm
An alarm activates the output. There are
no warnings.
[10]
Alarm or
warning
An alarm or a warning activates the
output.
[11]
At torque
limit
The torque limit set in
or
has been exceeded.
[12]
Out of
current range
The motor current is outside the range set
in
.
[13]
Below
current, low
The motor current is lower than set in
.
[14]
Above
current, high
The motor current is higher than set in
.
[15]
Out of speed
range
The output speed is outside the range set
in
and
.
[16]
Below speed,
low
The output speed is lower than the setting
in
[17]
Above speed,
high
The output speed is higher than the
setting in
.
[18]
Out of
feedback
range
The feedback is outside the range set in
and
Parameter Description
VLT
®
HVAC Drive Programming Guide
66
MG.11.CC.02 - VLT
®
is a registered Danfoss trademark
3
3