4-53 Warning Speed High
Range:
Function:
Size
related
*
[ par.
4-52 -
par. 4-13
RPM]
Enter the n
HIGH
value. When the motor
speed exceeds this limit (n
HIGH
), the
display reads SPEED HIGH. The signal
outputs can be programmed to produce a
status signal on terminal 27 or 29 and on
relay output 01 or 02. Programme the
upper signal limit of the motor speed,
n
HIGH
, within the normal working range of
the frequency converter. Refer to .
NOTE
Any changes in
4-13 Motor Speed High Limit [RPM]
will reset
the value in
to the same value as
set in
4-13 Motor Speed High Limit [RPM]
If a different value is needed in
, it
must be set after programming of
4-54 Warning Reference Low
Range:
Function:
-999999.999
*
[ -999999.999 -
par. 4-55 ]
Enter the lower reference limit.
When the actual reference falls
below this limit, the display
indicates Ref Low. The signal
outputs can be programmed to
produce a status signal on
terminal 27 or 29 and on relay
output 01 or 02.
4-55 Warning Reference High
Range:
Function:
999999.999
*
[ par. 4-54 -
999999.999 ]
Enter the upper reference limit.
When the actual reference
exceeds this limit, the display
reads Ref High. The signal
outputs can be programmed to
produce a status signal on
terminal 27 or 29 and on relay
output 01 or 02.
4-56 Warning Feedback Low
Range:
Function:
-999999.999
ProcessCtrlUnit
*
[ -999999.999 -
par. 4-57
ProcessCtrlUnit]
Enter the lower feedback
limit. When the feedback
falls below this limit, the
display reads Feedb Low.
The signal outputs can be
programmed to produce a
status signal on terminal
27 or 29 and on relay
output 01 or 02.
4-57 Warning Feedback High
Range:
Function:
999999.999
ProcessCtrlUnit
*
[ par. 4-56 -
999999.999
ProcessCtrlUnit]
Enter the upper feedback
limit. When the feedback
exceeds this limit, the
display reads Feedb High.
The signal outputs can be
programmed to produce
a status signal on terminal
27 or 29 and on relay
output 01 or 02.
4-58 Missing Motor Phase Function
Option:
Function:
Displays an alarm in the event of a missing
motor phase.
[0]
Disabled
No alarm is displayed if a missing motor
phase occurs.
[2]
*
Trip 1000 ms
NOTE
This parameter cannot be adjusted while the motor is
running.
3.6.3 4-6* Speed Bypass
Some systems call for avoiding certain output frequencies
or speeds, due to resonance problems in the system. A
maximum of four frequency or speed ranges can be
avoided.
4-60 Bypass Speed From [RPM]
Array [4]
Range:
Function:
Size related
*
[ 0 - par. 4-13
RPM]
Some systems call for avoiding
certain output speeds due to
resonance problems in the system.
Enter the lower limits of the
speeds to be avoided.
4-61 Bypass Speed From [Hz]
Array [4]
Range:
Function:
Size related
*
Application
dependent
*
[ 0.0 - par. 4-14
Hz]
[Application
dependant]
Some systems call for
avoiding certain output
speeds due to resonance
problems in the system.
Enter the lower limits of
the speeds to be
avoided.
Parameter Description
VLT
®
HVAC Drive Programming Guide
60
MG.11.CC.02 - VLT
®
is a registered Danfoss trademark
3