[62] Reset Counter
A
Input for reset of counter A.
[63] Counter B (up) (Terminal 29 and 33 only) Input for
increment counting in the SLC counter.
[64] Counter B
(down)
(Terminal 29 and 33 only) Input for
decrement counting in the SLC counter.
[65] Reset Counter
B
Input for reset of counter B.
[66] Sleep Mode
Forces frequency converter into Sleep Mode
(see parameter group 22-4*). Reacts on the
rising edge of signal applied!
[68] Timed Actions
Disabled
Timed actions are disabled. See parameter
group
23-0* Timed Actions
.
[69] Constant OFF
Timed Actions
are set for Constant OFF. See
parameter group
23-0* Timed Actions
.
[70] Constant ON
Timed Actions
are set for Constant ON. See
parameter group
23-0* Timed Actions
.
[78] Reset
Preventive
Maintenance
Word
Resets all data in
to 0.
[80] PTC Card 1
All Digital Inputs can be set to PTC Card 1
[80]. However, only one Digital Input must
be set to this choice.
5-10 Terminal 18 Digital Input
Same options and functions as parameter group 5-1*, except for
Pulse input
.
Option:
Function:
[8]
*
Start
5-11 Terminal 19 Digital Input
Same options and functions as parameter group 5-1*, except for
Pulse input
.
Option:
Function:
[0]
*
No operation
5-12 Terminal 27 Digital Input
Option:
Function:
[2]
*
Coast inverse Functions are described under parameter
group 5-1*
Digital Inputs
5-13 Terminal 29 Digital Input
Option:
Function:
Select the function from the available digital input
range and the additional options [60], [61], [63] and
[64]. Counters are used in Smart Logic Control
functions.This parameter is available for only.
[14]
*
Jog Functions are described under 5-1*
Digital Inputs
5-14 Terminal 32 Digital Input
Option:
Function:
[0]
*
No Operation Same options and functions as parameter
group 5-1*
Digital Inputs
, except for
Pulse
input
.
5-15 Terminal 33 Digital Input
Option:
Function:
[0]
*
No Operation Same options and functions as parameter
group 5-1*
Digital Inputs
.
5-16 Terminal X30/2 Digital Input
This parameter is active when option module MCB 101 is
installed in the frequency converter. Same options and functions
as parameter group 5-1* except for
Pulse input
[32].
Option:
Function:
[0]
*
No operation
5-17 Terminal X30/3 Digital Input
This parameter is active when option module MCB 101 is
installed in the frequency converter. Same options and functions
as parameter group 5-1* except for
Pulse input
[32].
Option:
Function:
[0]
*
No operation
5-18 Terminal X30/4 Digital Input
This parameter is active when option module MCB 101 is
installed in the frequency converter. Same options and functions
as parameter group 5-1* except for
Pulse input
[32].
Option:
Function:
[0]
*
No operation
5-19 Terminal 37 Safe Stop
Option:
Function:
[1]
*
Safe Stop
Alarm
Coasts frequency converter when safe stop is
activated. Manual reset from LCP, digital
input or fieldbus.
[3]
Safe Stop
Warning
Coasts frequency converter when safe stop is
activated (T-37 off). When safe stop circuit is
reestablished, the frequency converter will
continue without manual reset.
[4]
PTC 1 Alarm Coasts frequency converter when safe stop is
activated. Manual reset from LCP, digital
input or fieldbus. Choice 4 is only available
when the MCB 112 PTC Thermistor Card is
connected.
[5]
PTC 1
Warning
Coasts frequency converter when safe stop is
activated (T-37 off). When safe stop circuit is
reestablished, the frequency converter will
continue without manual reset, unless a
Digital Input set to PTC Card 1 [80] is still
enabled. Choice 5 is only available when the
MCB 112 PTC Thermistor Card is connected.
[6]
PTC 1 &
Relay A
This choice is used when the PTC option is
gated together with a Stop button through a
Safety relay to T-37. Coasts frequency
converter when safe stop is activated. Manual
reset from LCP, digital input or fieldbus.
Choice 6 is only available when the MCB 112
PTC Thermistor Card is connected.
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CC.02 - VLT
®
is a registered Danfoss trademark
65
3
3