20-20 Feedback Function
Option:
Function:
NOTE
Any unused feedbacks must be set to
No
Function
in
,
, or
. Only setpoint 1 will be used. The
sum of Setpoint 1 and any other
references that are enabled (see meter
group 3-1*) will be used as the PID
Controller’s setpoint reference.
[4] Maximum
Maximum
[4] sets up the PID Controller to com
Feedback 1, Feedback 2 and Feedback 3 and
use the highest value as the feedback.
NOTE
Any unused feedbacks must be set to
No
Function
in
,
, or
Only Setpoint 1 will be used. The sum of
Setpoint 1 and any other references that are
enabled (see meter group 3-1*) will be used as
the PID Controller’s setpoint reference.
[5] Multi
Setpoint
Min
Multi-setpoint minimum
[5] sets up the PID
Controller to calculate the difference between
Feedback 1 and Setpoint 1, Feedback 2 and
Setpoint 2, and Feedback 3 and Setpoint 3. It
will use the feedback/setpoint pair in which the
feedback is the farthest below its corresponding
setpoint reference. If all feedback signals are
above their corresponding setpoints, the PID
Controller will use the feedback/setpoint pair in
which the difference between the feedback and
setpoint is the least.
NOTE
If only two feedback signals are used, the
feedback that is not to be used must be
set to
No Function
in
or
. Note that each
setpoint reference will be the sum of its
respective meter value (
and
) and
any other references that are enabled (see
meter group 3-1*).
[6] Multi
Setpoint
Max
Multi-setpoint maximum
[6] sets up the PID
Controller to calculate the difference between
Feedback 1 and Setpoint 1, Feedback 2 and
Setpoint 2, and Feedback 3 and Setpoint 3. It
will use the feedback/setpoint pair in which the
feedback is farthest above its corresponding
20-20 Feedback Function
Option:
Function:
setpoint reference. If all feedback signals are
below their corresponding setpoints, the PID
Controller will use the feedback/setpoint pair in
which the difference between the feedback and
the setpoint reference is the least.
NOTE
If only two feedback signals are used, the
feedback that is not to be used must be
set to
No Function
in
,
or
. Note that each
setpoint reference will be the sum of its
respective meter value (
,
and
) and
any other references that are enabled (see
meter group 3-1*).
NOTE
Any unused feedback must be set to “No function” in its
Feedback Source meter:
,
or
The feedback resulting from the function selected in
will be used by the PID Controller
to control the output frequency of the frequency
converter. This feedback can also be shown on the
frequency converter’s display, be used to control a
frequency converter's analog output, and be transmitted
over various serial communication protocols.
The frequency converter can be configured to handle multi
zone applications. Two different multi zone applications
are supported:
•
Multi zone, single setpoint
•
Multi zone, multi setpoint
Parameter Description
VLT
®
HVAC Drive Programming Guide
132
MG.11.CC.02 - VLT
®
is a registered Danfoss trademark