2.1.6 Function Set-ups
The Function set-up provides quick and easy access to all parameters required for the majority of VLT
®
HVAC Drive
applications including most VAV and CAV supply and return fans, cooling tower fans, Primary, Secondary and Condenser
Water Pumps and other pump, fan and compressor applications.
How to access Function set-up - example
Step 1: Turn on the frequency converter (yellow LED lights)
28.8%
14.4Hz
Auto Remote Running
5.66A
2.63kW
0kWh
1 (1)
130B
T110.11
Status
Step 2: Press the [Quick Menus] button (Quick Menus
choices appear).
130B
T111.10
Q1 My Personal Menu
Q2 Quick Setup
Q3 Function Setups
Q5 Changes Made
13.7% 13.0A 1(1)
Quick Menus
Step 3: Use the up/down navigation keys to scroll down to
Function set-ups. Press [OK].
130B
T112.10
Q1 My Personal Menu
Q2 Quick Setup
Q3 Function Setups
Q5 Changes Made
69.3% 5.20A 1(1)
Quick Menus
Step 4: Function set-ups choices appear. Choose Q3-1
General Settings
. Press [OK].
Q3
130B
T113.10
Q3-1 General Settings
Q3-2 Open Loop Settings
Q3-3 Closed Loop Settings
Q3-4 Application Settings
28.4% 2.05A 1(1)
Function Setups
Step 5: Use the up/down navigation keys to scroll down to
i.e. Q3-11
Analog Outputs
. Press [OK].
130B
T114.10
26.0%
Q3 - 10 Adv. Motor Settings
Q3 - 11 Analog Output
Q3 - 12 Clock Settings
Q3 - 13 Display Settings
7.14A
1(1)
Q3-1
General Settings
Step 6: Choose
. Press [OK].
130BA115.10
6 - 50 Terminal 42 Output
(100) Output frequency
26.3% 5.82A 1(1)
Analog Output
03.11
Step 7: Use the up/down navigation keys to select
between the different choices. Press [OK].
130B
T116.10
43.4%
6-50 Terminal 42 Output
[107]
Speed
Analog Output
7.99A
Q3-11
1(1)
How to Programme
VLT
®
HVAC Drive Programming Guide
MG.11.CC.02 - VLT
®
is a registered Danfoss trademark
17