5-66 Terminal X30/6 Pulse Output Variable
Select the variable for read-out on terminal X30/6.
This parameter cannot be adjusted while the motor is running.
This parameter is active when option module MCB 101 is
installed in the frequency converter.
Same options and functions as parameter group 5-6*.
Option:
Function:
[0]
*
No operation
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[51]
MCO controlled
[100]
Output frequency
[101]
Reference
[102]
Feedback
[103]
Motor current
[104]
Torque rel to limit
[105]
Torq relate to rated
[106]
Power
[107]
Speed
[108]
Torque
[109]
Max Out Freq
[119]
Torque % lim
5-68 Pulse Output Max Freq #X30/6
Select the maximum frequency on terminal X30/6 referring to
the output variable in
5-66 Terminal X30/6 Pulse Output Variable
.
This parameter cannot be adjusted while the motor is running.
This parameter is active when option module MCB 101 is
mounted in the frequency converter.
Range:
Function:
5000. Hz
*
[0 - 32000 Hz]
3.7.8 5-9* Bus Controlled
This parameter group selects digital and relay outputs via
a fieldbus setting.
5-90 Digital & Relay Bus Control
Range:
Function:
0
*
[0 -
2147483647 ]
This parameter holds the state of the
digital outputs and relays that is controlled
by bus.
A logical '1' indicates that the output is
high or active.
A logical '0' indicates that the output is low
or inactive.
5-90 Digital & Relay Bus Control
Range:
Function:
Bit 0
CC Digital Output Terminal 27
Bit 1
CC Digital Output Terminal 29
Bit 2
GPIO Digital Output Terminal X
30/6
Bit 3
GPIO Digital Output Terminal X
30/7
Bit 4
CC Relay 1 output terminal
Bit 5
CC Relay 2 output terminal
Bit 6
Option B Relay 1 output terminal
Bit 7
Option B Relay 2 output terminal
Bit 8
Option B Relay 3 output terminal
Bit 9-15 Reserved for future terminals
Bit 16
Option C Relay 1 output terminal
Bit 17
Option C Relay 2 output terminal
Bit 18
Option C Relay 3 output terminal
Bit 19
Option C Relay 4 output terminal
Bit 20
Option C Relay 5 output terminal
Bit 21
Option C Relay 6 output terminal
Bit 22
Option C Relay 7 output terminal
Bit 23
Option C Relay 8 output terminal
Bit
24-31
Reserved for future terminals
5-93 Pulse Out #27 Bus Control
Range:
Function:
0.00 %
*
[0.00 - 100.00
%]
Contains the frequency to apply to
the digital output terminal 27, when
it is configured as [Bus Controlled].
5-94 Pulse Out #27 Timeout Preset
Range:
Function:
0.00 %
*
[0.00 - 100.00
%]
Contains the frequency to apply to
the digital output terminal 27, when
it is configured as [Bus Controlled
Timeout] and timeout is detected.
5-95 Pulse Out #29 Bus Control
Range:
Function:
0.00 %
*
[0.00 - 100.00
%]
Contains the frequency to apply to
the digital output terminal 29, when
it is configured as [Bus Controlled].
5-96 Pulse Out #29 Timeout Preset
Range:
Function:
0.00 %
*
[0.00 - 100.00
%]
Contains the frequency to apply to
the digital output terminal 29, when
it is configured as [Bus Controlled
Timeout] and timeout is detected
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CC.02 - VLT
®
is a registered Danfoss trademark
73