1-20 Motor Power [kW]
Range:
Function:
Size
related
*
[ 0.09 -
3000.00
kW]
Enter the nominal motor power in kW
according to the motor nameplate data.
The default value corresponds to the
nominal rated output of the unit.
This parameter cannot be adjusted
while the motor is running. Depending
on the choices made in
, either
or
is made invisible.
1-21 Motor Power [HP]
Range:
Function:
Size
related
*
[ 0.09 -
3000.00 hp]
Enter the nominal motor power in HP
according to the motor nameplate data.
The default value corresponds to the
nominal rated output of the unit.
This parameter cannot be adjusted
while the motor is running.
Depending on the choices made in
, either
or
is
made invisible.
1-22 Motor Voltage
Range:
Function:
Size
related
*
[ 10. -
1000. V]
Enter the nominal motor voltage
according to the motor nameplate
data. The default value corresponds to
the nominal rated output of the unit.
This parameter cannot be adjusted
while the motor is running.
1-23 Motor Frequency
Range:
Function:
Size
related
*
[20 -
1000 Hz]
Select the motor frequency value from
the motor nameplate data.For 87 Hz
operation with 230/400 V motors, set the
nameplate data for 230 V/50 Hz. Adapt
4-13 Motor Speed High Limit [RPM]
and
3-03 Maximum Reference
to the 87 Hz
application.
NOTE
This parameter cannot be adjusted while the motor is
running.
1-24 Motor Current
Range:
Function:
Size
related
*
[ 0.10 -
10000.00 A]
Enter the nominal motor current
value from the motor nameplate
data. This data is used for
calculating motor torque, motor
thermal protection etc.
NOTE
This parameter cannot be adjusted while the motor is
running.
1-25 Motor Nominal Speed
Range:
Function:
Size related
*
[100 - 60000
RPM]
Enter the nominal motor speed
value from the motor nameplate
data. This data is used for
calculating automatic motor
compensations.
NOTE
This parameter cannot be adjusted while the motor is
running.
1-26 Motor Cont. Rated Torque
Range:
Function:
Size
related
*
[0.1 -
10000.0 Nm]
Enter the value from the motor
nameplate data. The default value
corresponds to the nominal rated
output. This parameter is available
when
is set to
PM, non salient SPM [1]
, i.e. the
parameter is valid for PM and
nonsalient SPM motors only.
1-28 Motor Rotation Check
Option:
Function:
Following installation and connection of the
motor, this function allows the correct motor
rotation direction to be verified. Enabling this
function overrides any bus commands or digital
inputs, except External Interlock and Safe Stop (if
included).
[0]
*
Off
Motor Rotation Check is not active.
[1]
Enabled Motor Rotation Check is enabled. Once enabled,
Display shows:
“Note! Motor may run in wrong direction”.
Pressing [OK], [Back] or [Cancel] will dismiss the message
and display a new message: “Press [Hand on] to start the
motor. Press [Cancel] to abort”. Pressing [Hand on] starts
the motor at 5 Hz in forward direction and the display
shows: “Motor is running. Check if motor rotation direction
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CC.02 - VLT
®
is a registered Danfoss trademark
39
3