24-93 Missing Motor Coefficient 3
Range:
Function:
0.0000
*
[-100.0000 -
100.0000 ]
Enter the linear coefficient of
the Missing Motor detection
function.
24-94 Missing Motor Coefficient 4
Range:
Function:
0.000
*
[-500.000 - 500.000 ] Enter the constant of the Missing
Motor detection function.
24-95 Locked Rotor Function
Option:
Function:
Select the action to be taken if the motor current
is above the limit calculated as a function of the
output frequency. The function is used for
detecting e.g. a locked rotor in multi-motor
applications.
[0]
*
Off
[1]
Warning
24-96 Locked Rotor Coefficient 1
Range:
Function:
0.0000
*
[-10.0000 -
10.0000 ]
Enter the cubic coefficient of the
Locked Rotor detection function
multiplied by 1000.
24-97 Locked Rotor Coefficient 2
Range:
Function:
0.0000
*
[-100.0000 -
100.0000 ]
Enter the quadratic coefficient of
the Locked Rotor detection
function multiplied by 1000.
24-98 Locked Rotor Coefficient 3
Range:
Function:
0.0000
*
[-100.0000 -
100.0000 ]
Enter the linear coefficient of
the Locked Rotor detection
function.
24-99 Locked Rotor Coefficient 4
Range:
Function:
0.000
*
[-500.000 - 500.000 ] Enter the constant of the Locked
Rotor detection function.