No.
Description
Warning
Alarm
Trip lock
Cause
55
AMA parameter range
X
The parameter values of the motor are outside of the
acceptable range. AMA does not run.
56
AMA interrupt
X
The AMA.
57
AMA timeout
X
Run the AMA again.
58
AMA internal
X
Contact Danfoss.
59
Current limit
X
X
Frequency converter overload.
61
Encoder loss
X
X
63
Mechanical brake low
X
Actual motor current has not exceeded the release brake
current within start delay time window.
65
Control card temp
X
X
X
The cut-out temperature of the control card is 80
°
C.
67
Option change
X
A new option is detected, or a mounted option is removed.
69
Power card temp
X
X
X
The difference between the speed reference and the
feedback exceeds the limit.
80
Drive initialised to default
value
X
All parameters are initialised to default settings.
87
Auto DC braking
X
Occurs in IT mains when the frequency converter coasts and
the voltage is higher than 830 V. Energy on the DC link is
consumed by the motor. This function can be enabled/
disabled in
parameter 0-07 Auto DC Braking
.
88
Option detection
X
X
An option is removed successfully.
90
Feedback monitor
X
X
Option B detects a feedback fault.
95
Broken belt
X
X
101
Flow/pressure information
missing
X
X
120
Position control fault
X
250
New spare part
X
X
251
New type code
X
X
252
Tension limit
X
nw
run
Not while running
The parameter can only be changed when the motor is
stopped.
Err.
A wrong password was
entered
Occurs when using a wrong password for changing a
password-protected parameter.
Table 6.2 Warnings and Alarms Code List
1) These faults can be caused by mains distortions. Installing Danfoss line filter could fix this problem.
The alarm words, warning words and extended status
words can be accessed via fieldbus or optional fieldbus for
diagnosis.
WARNING/ALARM 2, Live zero error
This warning or alarm only appears if programmed in
parameter 6-01 Live Zero Timeout Function
. The signal on 1
of the analog inputs is less than 50% of the minimum
value programmed for that input. Broken wiring or faulty
device sending the signal can cause this condition.
Troubleshooting
•
Check connections on all the analog input
terminals. Control card terminals 53 and 54 for
signals, terminal 55 common.
•
Check that the frequency converter programming
and switch settings match the analog signal type.
•
Perform the input terminal signal test.
WARNING/ALARM 4, Mains phase loss
A phase is missing on the supply side, or the mains
voltage imbalance is too high. This message also appears
for a fault in the input rectifier on the frequency converter.
Options are programmed in
parameter 14-12 Function at
Mains Imbalance
.
Troubleshooting
•
Check the supply voltage and supply currents to
the frequency converter.
WARNING/ALARM 7, DC overvoltage
If the DC-link voltage exceeds the limit, the frequency
converter trips after a time.
Troubleshooting
•
Extend the ramp time.
•
Change the ramp type.
Troubleshooting
VLT
®
AutomationDrive FC 360
146