0-30 Custom Readout Unit
Option:
Function:
[11]
RPM
[12]
Pulse/s
[20]
l/s
[21]
l/min
[22]
l/h
[23]
m³/s
[24]
m³/min
[25]
m³/h
[30]
kg/s
[31]
kg/min
[32]
kg/h
[33]
t/min
[34]
t/h
[40]
m/s
[41]
m/min
[45]
m
[60]
°C
[70]
mbar
[71]
bar
[72]
Pa
[73]
kPa
[74]
m WG
[80]
kW
[120] GPM
[121] gal/s
[122] gal/min
[123] gal/h
[124] CFM
[127] ft³/h
[140] ft/s
[141] ft/min
[160] °F
[170] psi
[171] lb/in2
[172] in WG
[173] ft WG
[180] HP
0-31 Custom Readout Min Value
Range:
Function:
0 CustomRea-
doutUnit
*
[ 0 -
999999.99
CustomRea-
doutUnit]
This parameter sets the
minimum value of the custom
readout (occurs at zero speed). It
is only possible to select a value
different from 0 when selecting a
linear unit in
parameter 0-30 Custom Readout
Unit
. For quadratic and cubic
units, the minimum value is 0.
0-32 Custom Readout Max Value
Range:
Function:
100 Custom-
ReadoutUnit
*
[ 0.0 -
999999.99
CustomRea-
doutUnit]
This parameter sets the
maximum value to be shown
when the motor speed has
reached the value set for
parameter 4-14 Motor Speed
High Limit [Hz]
.
4.1.5 0-4* LCP Keypad
Enable, disable, and password protect individual keys on
the LCP.
0-40 [Hand on] Key on LCP
Option:
Function:
[0]
Disabled Avoid accidental start of the frequency converter
in
Hand On
mode.
[1]
*
Enabled [Hand On] is enabled.
0-42 [Auto on] Key on LCP
Option:
Function:
[0]
Disabled Avoid accidental start of the freqeuncy converter
from LCP.
[1]
*
Enabled [Hand On] is enabled.
0-44 [Off/Reset] Key on LCP
Option:
Function:
[0]
Disabled
[1]
*
Enabled
[7]
Enable Reset Only
4.1.6 0-5* Copy/Save
Copy parameters from and to LCP and GLCP. Use these
parameters for saving and copying set-ups from 1
frequency converter to another.
0-50 LCP Copy
Option:
Function:
[0]
*
No copy
No function.
[1]
All to LCP
Copies all parameters in all set-ups from the
frequency converter memory to the LCP. For
service purposes, copy all parameters to the
LCP after commissioning.
[2]
All from
LCP
Copies all parameters in all set-ups from the
LCP memory to the frequency converter
memory.
[3]
Size indep.
from LCP
Copies only the parameters that are
independent of the motor size. This selection
can be used to program several frequency
converters with the same function without
disturbing motor data that is already set.
Parameter Descriptions
VLT
®
AutomationDrive FC 360
24
Danfoss A/S © 7/2015 All rights reserved.
MG06C602