4.16 Parameters: 17-** Feedback Options
4.16.1 17-1* Inc.Enc.Interface
17-10 Signal Type
Option:
Function:
[0]
None
[1]
*
RS422 (5V TTL)
[2]
Sinusoidal 1Vpp
17-11 Resolution (PPR)
Range:
Function:
1024
*
[10 - 10000 ] Enter the resolution of the incremental
track, which is the number of pulses or
periods per revolution.
4.16.2 17-5* Resolver Interface
17-50 Poles
Range:
Function:
2
*
[2 - 2 ]
17-51 Input Voltage
Range:
Function:
7 V
*
[2 - 8 V]
17-52 Input Frequency
Range:
Function:
10 kHz
*
[2 - 15 kHz]
17-53 Transformation Ratio
Range:
Function:
0.5
*
[0.1 - 1.1 ]
17-56 Encoder Sim. Resolution
Option:
Function:
[0]
*
Disabled
[1]
512
[2]
1024
[3]
2048
[4]
4096
17-59 Resolver Interface
Option:
Function:
[0]
*
Disabled
[1]
Enabled
4.16.3 17-6* Monitoring and App.
17-60 Feedback Direction
Option:
Function:
[0]
*
Clockwise
[1]
Counter clockwise
17-61 Feedback Signal Monitoring
Option:
Function:
[0]
Disabled
[1]
*
Warning
[2]
Trip
[3]
Jog
[4]
Freeze Output
[5]
Max Speed
[6]
Switch to Open Loop
Parameter Descriptions
VLT
®
AutomationDrive FC 360
106
Danfoss A/S © 7/2015 All rights reserved.
MG06C602
4