1-29 Automatic Motor Adaption (AMA)
Option:
Function:
NOTICE
This parameter cannot be adjusted while
the motor is running.
NOTICE
Terminal 27 digital input
(
parameter 5-12 Terminal 27 Digital Input
)
has coast inverse as the default setting.
This setting means that AMA cannot be
performed if terminal 27 is switched off.
The AMA function optimises dynamic motor
performance by automatically optimising the
advanced motor
parameter 1-30 Stator Resistance
to
parameter 1-35 Main Reactance (Xh)
while
the motor is stationary.
[0]
*
Off
No function.
[1] Enable
Complete
AMA
Depending on the option selected in
parameter 1-10 Motor Construction
, the AMA is
performed on different parameters.
•
If
[0] Asynchron
is selected, the AMA is
performed on:
-
Parameter 1-30 Stator
Resistance (Rs)
-
Parameter 1-35 Main Reactance
(Xh)
•
If
[1] PM, non salient SPM, non Sat
is
selected, the AMA is performed on:
-
Parameter 1-30 Stator
Resistance (Rs)
-
Parameter 1-37 d-axis
Inductance (Ld)
•
If
[2] PM, salient IPM, non Sat
is selected,
the AMA is performed on:
-
Parameter 1-30 Stator
Resistance (Rs)
-
Parameter 1-37 d-axis
Inductance (Ld)
-
Parameter 1-38 q-axis
Inductance (Lq)
•
If
[3] PM, salient IPM, Sat
is selected, the
AMA is performed on:
-
Parameter 1-30 Stator
Resistance (Rs)
-
Parameter 1-37 d-axis
Inductance (Ld)
1-29 Automatic Motor Adaption (AMA)
Option:
Function:
-
Parameter 1-38 q-axis
Inductance (Lq)
-
Parameter 1-44 d-axis
Inductance Sat. (LdSat)
-
Parameter 1-45 q-axis
Inductance Sat. (LqSat)
[2] Enable
Reduced
AMA
Performs a reduced AMA of the stator resistance
R
s
(
parameter 1-30 Stator Resistance (Rs)
) in the
system only. If an LC filter is used between the
frequency converter and the motor, select this
option.
When
parameter 1-10 Motor Construction
is set to options
that enable permanent motor mode, the only option
available is
[1] Enable Complete AMA
.
Activate the AMA function by pressing [Hand On] after
selecting
[1] Enable Complete AMA
or
[2] Enable Reduced
AMA
. After a normal sequence, the display reads:
Press [OK]
to finish AMA
. After pressing [OK], the frequency converter
is ready for operation.
NOTICE
•
For the best adaptation of the frequency
converter, run AMA on a cold motor.
•
AMA cannot be performed while the motor is
running.
NOTICE
Avoid generating external torque during AMA.
NOTICE
If one of the settings in parameter group
1-2* Motor
Data
is changed, the advanced motor parameters,
parameter 1-30 Stator Resistance (Rs)
to
, return to default setting.
If LC filter is used, set the frequency converter to run in U/f
control mode (recommended), or perform reduced AMA in
VVC
+
mode. If LC filter is not used, perform complete AMA.
4.2.4 1-3* Adv. Motor Data I
Set parameters for advanced motor data. The motor data
in parameters 1-30 to 1-39 must match the motor for
optimal performance. If the motor data is not known,
running an AMA is recommended.
Parameter Descriptions
VLT
®
AutomationDrive FC 360
30
Danfoss A/S © 7/2015 All rights reserved.
MG06C602
4
4