5.2.12 13-** Smart Logic Control
Par. No. # Parameter description
Default value
2-set-up
Change
during
operation
Conversion
index
Type
13-0* SLC Settings
13-00
SL Controller Mode
[0] Off
1 set-up
TRUE
–
Uint8
13-01
Start Event
[39] Start command
1 set-up
TRUE
–
Uint8
13-02
Stop Event
[40] Drive stopped
1 set-up
TRUE
–
Uint8
13-03
Reset SLC
[0] Do not reset SLC
1 set-up
TRUE
–
Uint8
13-1* Comparators
13-10
Comparator Operand
[0] Disabled
1 set-up
TRUE
–
Uint8
13-11
Comparator Operator
[1] Approx.Equal (~)
1 set-up
TRUE
–
Uint8
13-12
Comparator Value
0 N/A
1 set-up
TRUE
-3
Int32
13-2* Timers
13-20
SL Controller Timer
0 s
1 set-up
TRUE
-2
Uint32
13-4* Logic Rules
13-40
Logic Rule Boolean 1
[0] False
1 set-up
TRUE
–
Uint8
13-41
Logic Rule Operator 1
[0] Disabled
1 set-up
TRUE
–
Uint8
13-42
Logic Rule Boolean 2
[0] False
1 set-up
TRUE
–
Uint8
13-43
Logic Rule Operator 2
[0] Disabled
1 set-up
TRUE
–
Uint8
13-44
Logic Rule Boolean 3
[0] False
1 set-up
TRUE
–
Uint8
13-5* States
13-51
SL Controller Event
[0] False
1 set-up
TRUE
–
Uint8
13-52
SL Controller Action
[0] Disabled
1 set-up
TRUE
–
Uint8
5.2.13 14-** Special Functions
Par. No. # Parameter description
Default value
4-set-up
Change
during
operation
Conversion
index
Type
14-0* Inverter Switching
14-01
Switching Frequency
ExpressionLimit
All set-ups
TRUE
-
Uint8
14-03
Overmodulation
[1] On
All set-ups
FALSE
-
Uint8
14-07
Dead Time Compensation Level
ExpressionLimit
All set-ups
FALSE
0
Uint8
14-08
Damping Gain Factor
ExpressionLimit
All set-ups
TRUE
0
Uint8
14-09
Dead Time Bias Current Level
ExpressionLimit
All set-ups
FALSE
0
Uint8
14-1* Mains On/Off
14-10
Mains Failure
[0] No function
All set-ups
FALSE
-
Uint8
14-11
Mains Voltage at Mains Fault
342 V
All set-ups
TRUE
0
Uint16
14-12
Function at Mains Imbalance
[0] Trip
1 set-up
TRUE
-
Uint8
14-15
Kin. Backup Trip Recovery Level
ExpressionLimit
All set-ups
TRUE
-3
Uint32
14-2* Reset Functions
14-20
Reset Mode
[0] Manual reset
All set-ups
TRUE
-
Uint8
14-21
Automatic Restart Time
10 s
All set-ups
TRUE
0
Uint16
14-22
Operation Mode
[0] Normal operation
1 set-up
TRUE
-
Uint8
14-24
Trip Delay at Current Limit
60 s
All set-ups
TRUE
0
Uint8
14-25
Trip Delay at Torque Limit
60 s
All set-ups
TRUE
0
Uint8
14-27
Action At Inverter Fault
[1] Warning
All set-ups
TRUE
-
Uint8
14-28
Production Settings
[0] No action
1 set-up
FALSE
-
Uint8
14-29
Service Code
0 N/A
1 set-up
TRUE
0
Uint32
14-3* Current Limit Ctrl.
14-30
Current Lim Ctrl, Proportional Gain
100%
All set-ups
TRUE
0
Uint16
14-31
Current Lim Ctrl, Integration Time
0.020 s
All set-ups
TRUE
-3
Uint16
Parameter Lists
VLT
®
AutomationDrive FC 360
134
Danfoss A/S © 7/2015 All rights reserved.
MG06C602