5-53 Term. 29 High Ref./Feedb. Value
Range:
Function:
Size
related
*
[-4999 -
4999 ]
Enter the high reference value [Hz] for the
motor shaft speed, and the high feedback
value. See also
. Select terminal 29
as a digital input (
parameter 5-02 Terminal
29 Mode
=
[0] Input
(default) and
parameter 5-13 Terminal 29 Digital
Input
=applicable value).
5-55 Term. 33 Low Frequency
Range:
Function:
4 Hz
*
[4 - 31999
Hz]
Enter the low frequency corresponding to
the low motor shaft speed (which is low
reference value) in
5-56 Term. 33 High Frequency
Range:
Function:
32000
Hz
*
[5 - 32000
Hz]
Enter the high frequency corresponding
to the high motor shaft speed (that is
high reference value) in
parameter 5-58 Term. 33 High Ref./Feedb.
Value
5-57 Term. 33 Low Ref./Feedb. Value
Range:
Function:
0
*
[-4999 -
4999 ]
Enter the low reference value [Hz] for the
motor shaft speed. This value is also the low
feedback value, see also
5-58 Term. 33 High Ref./Feedb. Value
Range:
Function:
Size related
*
[-4999 -
4999 ]
Enter the high reference value [Hz]
for the motor shaft speed. See also
parameter 5-53 Term. 29 High Ref./
Feedb. Value
.
4.6.6 5-6* Pulse Outputs
NOTICE
These parameters cannot be adjusted while the motor is
running.
Use these parameters to configure pulse outputs with their
functions and scaling. Terminal 27 and 29 are allocated to
pulse output via
parameter 5-01 Terminal 27 Mode
and
parameter 5-02 Terminal 29 Mode
.
Output value
Output
(Hz)
High output
value
P 5-60(term27)
P 5-63(term29)
High freq.
P 5-62(term27)
P 5-65(term29)
130BA089.11
Illustration 4.15 Configuration of Pulse Outputs
5-60 Terminal 27 Pulse Output Variable
Option:
Function:
[0]
*
No operation
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[100]
Output frequency
[101]
Reference
[102]
Process Feedback
[103]
Motor Current
[104]
Torque rel to limit
[105]
Torq relate to rated
[106]
Power
[107]
Speed
[109]
Max Out Freq
[113]
Ext. Closed Loop 1
5-62 Pulse Output Max Freq 27
Range:
Function:
5000 Hz
*
[4 - 32000
Hz]
Set the maximum frequency for terminal
27, corresponding to the output variable
selected in
5-63 Terminal 29 Pulse Output Variable
Option:
Function:
[0]
*
No operation
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[100]
Output frequency
[101]
Reference
[102]
Process Feedback
[103]
Motor Current
[104]
Torque rel to limit
[105]
Torq relate to rated
[106]
Power
[107]
Speed
[109]
Max Out Freq
[113]
Ext. Closed Loop 1
Parameter Descriptions
Programming Guide
MG06C602