5-40 Function Relay
Option:
Function:
parameter 37-00 Application Mode
is set
to
[1] Center winder
.
[193] Sleep Mode
The frequency converter/system has
entered sleep mode. See parameter
group
22-4* Sleep Mode
.
[194] Broken Belt
Function
A broken belt condition has been
detected. See parameter group
22-4*
Sleep Mode
.
5-41 On Delay, Relay
Array [2](Relay 1 [0], Relay 2 [1])
Range:
Function:
0.01 s
*
[0.01 - 600
s]
Enter the delay of the relay cut-in time.
The relay only cuts in if the condition in
parameter 5-40 Function Relay
is uninter-
rupted during the specified time.
Selected
Event
Relay
output
Selected
Event
Relay
output
On Delay
P 5-41
On Delay
P 5-41
Off Delay
P 5-42
130BA171.10
Illustration 4.12 On Delay, Relay
5-42 Off Delay, Relay
Array[2]: Relay1[0], Relay2[1]
Range:
Function:
0.01 s
*
[0.01 - 600 s] Enter the delay of the relay cut-out time.
Selected
Event
Relay
output
On Delay
P 5-41
Off Delay
P 5-42
130BA172.10
Illustration 4.13 Off Delay, Relay
If the selected event condition changes before the on- or
off delay timer expires, the relay output is unaffected.
4.6.5 5-5* Pulse Input
The pulse input parameters are used to define an
appropriate window for the impulse reference area by
configuring the scaling and filter settings for the pulse
inputs. Input terminals 29 or 33 act as frequency reference
inputs. Set terminal 29 (
parameter 5-13 Terminal 29 Digital
Input
) or terminal 33 (
parameter 5-15 Terminal 33 Digital
Input
) to
[32] Pulse input
. If terminal 29 is used as an input,
then set
parameter 5-01 Terminal 27 Mode
to
[0] Input
.
130BD377.10
Ref.
Low freq.
P 5-50/
P 5-55
Input
(Hz)
High
ref.
value
P 5-53/
p 5-58
High freq.
P 5-51/
P 5-56
Low
ref.
value
P 5-52/
p 5-57
Illustration 4.14 Pulse Input
5-50 Term. 29 Low Frequency
Range:
Function:
4 Hz
*
[4 - 31999
Hz]
Enter the low frequency limit corresponding
to the low motor shaft speed (that is low
reference value) in
. Refer to the
in this section.
5-51 Term. 29 High Frequency
Range:
Function:
32000
Hz
*
[5 - 32000
Hz]
Enter the high frequency limit
corresponding to the high motor shaft
speed (which is high reference value) in
parameter 5-53 Term. 29 High Ref./Feedb.
Value
.
5-52 Term. 29 Low Ref./Feedb. Value
Range:
Function:
0
*
[-4999 -
4999 ]
Enter the low reference value limit for the motor
shaft speed [Hz]. This value is also the lowest
feedback value, see also
. Set terminal 29 to digital
input (
parameter 5-02 Terminal 29 Mode
=
[0] Input
and
parameter 5-13 Terminal 29 Digital
=applicable value.
Parameter Descriptions
VLT
®
AutomationDrive FC 360
58
Danfoss A/S © 7/2015 All rights reserved.
MG06C602
4