4.6.8 5-9* Bus Controlled
This parameter group selects digital and relay outputs via a
fieldbus setting.
5-90 Digital & Relay Bus Control
Range:
Function:
0
*
[0 - 0xFFFFFFFF ] This parameter holds the state of the
digital outputs and relays that are
controlled by bus.
A logical 1 indicates that the output is
high or active.
A logical 0 indicates that the output is
low or inactive.
Bit 0–3
Reserved
Bit 4
Relay 1 output terminal
Bit 5
Relay 2 output terminal
Bit 6–23
Reserved
Bit 24
Terminal 42 digital output
Bit 25
Terminal 45 digital output
Bit 26–31
Reserved
Table 4.6 Bit Functions
5-93 Pulse Out 27 Bus Control
Range:
Function:
0 %
*
[0 -
100 %]
Set the output frequency transferred to the
output terminal 27 when the terminal is
configured as
[45] Bus Controlled
in
parameter 5-60 Terminal 27 Pulse Output
Variable
5-94 Pulse Out 27 Timeout Preset
Range:
Function:
0 %
*
[0 -
100 %]
Set the output frequency transferred to the
output terminal 27 when the terminal is
configured as
[48] Bus Ctrl Timeout
in
parameter 5-60 Terminal 27 Pulse Output Variable
and a time-out is detected.
5-95 Pulse Out 29 Bus Control
Range:
Function:
0 %
*
[0 -
100 %]
Set the output frequency transferred to the
output terminal 29 when the terminal is
configured as
[45] Bus Controlled
in
parameter 5-63 Terminal 29 Pulse Output
Variable
5-96 Pulse Out 29 Timeout Preset
Range:
Function:
0 %
*
[0 -
100 %]
Set the output frequency transferred to the
output terminal 29 when the terminal is
configured as
[48] Bus Ctrl Timeout
in
parameter 5-63 Terminal 29 Pulse Output
Variable
, and a time-out is detected.
Parameter Descriptions
Programming Guide
MG06C602
Danfoss A/S © 7/2015 All rights reserved.
61