5.2.5 4-** Limits/Warnings
Par. No. # Parameter description
Default value
2-set-up
Change
during
operation
Conversion
index
Type
4-1* Motor Limits
4-10
Motor Speed Direction
[2] Both directions
All set-ups
FALSE
–
Uint8
4-12
Motor Speed Low Limit [Hz]
0 Hz
All set-ups
FALSE
-1
Uint16
4-14
Motor Speed High Limit [Hz]
65 Hz
All set-ups
FALSE
-1
Uint16
4-16
Torque Limit Motor Mode
ExpressionLimit
All set-ups
TRUE
0
Uint16
4-17
Torque Limit Generator Mode
100%
All set-ups
TRUE
0
Uint16
4-18
Current Limit
ExpressionLimit
All set-ups
TRUE
0
Uint16
4-19
Max Output Frequency
ExpressionLimit
All set-ups
FALSE
-1
Uint16
4-2* Limit Factors
4-20
Torque Limit Factor Source
[0] No function
All set-ups
TRUE
–
Uint8
4-21
Speed Limit Factor Source
[0] No function
All set-ups
TRUE
–
Uint8
4-22
Break Away Boost
[0] Off
All set-ups
FALSE
–
Uint8
4-3* Motor Fb Monitor
4-30
Motor Feedback Loss Function
[0] Disabled
All set-ups
TRUE
–
Uint8
4-31
Motor Feedback Speed Error
20 Hz
All set-ups
TRUE
0
Uint16
4-32
Motor Feedback Loss Timeout
0.05 s
All set-ups
TRUE
-2
Uint16
4-4* Adj. Warnings 2
4-40
Warning Freq. Low
ExpressionLimit
All set-ups
TRUE
-1
Uint16
4-41
Warning Freq. High
ExpressionLimit
All set-ups
TRUE
-1
Uint16
4-42
Adjustable Temperature Warning
0 N/A
All set-ups
TRUE
0
Uint8
4-5* Adj. Warnings
4-50
Warning Current Low
0 A
All set-ups
TRUE
-2
Uint32
4-51
Warning Current High
ExpressionLimit
All set-ups
TRUE
-2
Uint32
4-54
Warning Reference Low
-4999 N/A
All set-ups
TRUE
-3
Int32
4-55
Warning Reference High
4999 N/A
All set-ups
TRUE
-3
Int32
4-56
Warning Feedback Low
-4999 ProcessCtrlUnit
All set-ups
TRUE
-3
Int32
4-57
Warning Feedback High
4999 ProcessCtrlUnit
All set-ups
TRUE
-3
Int32
4-58
Missing Motor Phase Function
[1] On
All set-ups
FALSE
–
Uint8
4-6* Speed Bypass
4-61
Bypass Speed From [Hz]
0 Hz
All set-ups
TRUE
-1
Uint16
4-63
Bypass Speed To [Hz]
0 Hz
All set-ups
TRUE
-1
Uint16
5.2.6 5-** Digital In/Out
Par. No. # Parameter description
Default value
2-set-up
Change
during
operation
Conversion
index
Type
5-0* Digital I/O mode
5-00
Digital I/O Mode
[0] PNP
1 set-up
FALSE
–
Uint8
5-01
Terminal 27 Mode
[0] Input
All set-ups
TRUE
–
Uint8
5-02
Terminal 29 Mode
[0] Input
All set-ups
TRUE
–
Uint8
5-1* Digital Inputs
5-10
Terminal 18 Digital Input
[8] Start
All set-ups
TRUE
–
Uint8
5-11
Terminal 19 Digital Input
[10] Reversing
All set-ups
TRUE
–
Uint8
5-12
Terminal 27 Digital Input
ExpressionLimit
All set-ups
TRUE
–
Uint8
5-13
Terminal 29 Digital Input
[14] Jog
All set-ups
TRUE
–
Uint8
5-14
Terminal 32 Digital Input
[0] No operation
All set-ups
TRUE
–
Uint8
5-15
Terminal 33 Digital Input
[16] Preset ref bit 0
All set-ups
TRUE
–
Uint8
5-16
Terminal 31 Digital Input
[0] No operation
All set-ups
TRUE
–
Uint8