5.2.16 17-** Feedback Options
Par. No. #
Parameter description
Default value
2-set-up
Change
during
operation
Conversion
index
Type
17-1* Inc.Enc.Interface
17-10
Signal Type
[1] RS422 (5 V TTL)
All set-ups
FALSE
–
Uint8
17-11
Resolution (PPR)
1024 N/A
All set-ups
FALSE
0
Uint16
17-5* Resolver Interface
17-50
Poles
2 N/A
1 set-up
FALSE
0
Uint8
17-51
Input Voltage
7 V
1 set-up
FALSE
-1
Uint8
17-52
Input Frequency
10 kHz
1 set-up
FALSE
2
Uint8
17-53
Transformation Ratio
0.5 N/A
1 set-up
FALSE
-1
Uint8
17-56
Encoder Sim. Resolution
[0] Disabled
1 set-up
FALSE
–
Uint8
17-59
Resolver Interface
[0] Disabled
All set-ups
FALSE
–
Uint8
17-6* Monitoring and App.
17-60
Feedback Direction
[0] Clockwise
All set-ups
FALSE
–
Uint8
17-61
Feedback Signal Monitoring
[1] Warning
All set-ups
TRUE
–
Uint8
5.2.17 18-** Data Readouts 2
Par.
No. #
Parameter description
Default value
4-set-up
Change
during
operation
Conversion
index
Type
18-8* Center Winder Readout
18-81 Tension PID Output
0 Hz
1 set-up
TRUE
-3
Int32
18-82 Center Winder Output
0 Hz
1 set-up
TRUE
-3
Int32
18-83 Line Speed
0 Hz
1 set-up
TRUE
-3
Int32
18-84 Diameter
0%
1 set-up
TRUE
-3
Int32
18-85 Tapered Tension Set Point
0%
1 set-up
TRUE
-1
Int32
18-86 Tension Feedback
0%
1 set-up
TRUE
-1
Int32
18-9* PID Readouts
18-90 Process PID Error
0%
All set-ups
FALSE
-1
Int16
18-91 Process PID Output
0%
All set-ups
FALSE
-1
Int16
18-92 Process PID Clamped Output
0%
All set-ups
FALSE
-1
Int16
18-93 Process PID Gain Scaled Output
0%
All set-ups
FALSE
-1
Int16
Parameter Lists
VLT
®
AutomationDrive FC 360
138
Danfoss A/S © 7/2015 All rights reserved.
MG06C602