8-54 Reversing Select
Option:
Function:
[2] Logic AND Activates the reverse command via the fieldbus/
serial communication port, and additionally via 1
of the digital inputs.
[3] Logic OR
Activates the reverse command via the fieldbus/
serial communication port, or via 1 of the digital
inputs.
8-55 Set-up Select
Option:
Function:
Select control of the frequency converter set-up
selection via the terminals (digital input) and/or
via the fieldbus.
[0]
Digital
input
Activates the set-up selection via a digital input.
[1]
Bus
Activates the set-up selection via the serial
communication port or fieldbus option.
[2]
Logic
AND
Activates the set-up selection via the fieldbus/
serial communication port, and via 1 of the
digital inputs.
[3]
*
Logic OR
Activates the set-up selection via the fieldbus/
serial communication port, or via 1 of the
digital inputs.
8-56 Preset Reference Select
Option:
Function:
Select control of the preset reference selection
via the terminals (digital input) and/or via the
fieldbus.
[0]
Digital
input
Activates preset reference selection via a digital
input.
[1]
Bus
Activates preset reference selection via the
serial communication port or fieldbus option.
[2]
Logic AND Activates preset reference selection via the
fieldbus/serial communication port, and via 1 of
the digital inputs.
[3]
*
Logic OR
Activates the preset reference selection via the
fieldbus/serial communication port, or via 1 of
the digital inputs.
8-57 Profidrive OFF2 Select
Select control of the frequency converter OFF2 selection via the
terminals (digital input) and/or via the fieldbus. This parameter is
active only when
parameter 8-01 Control Site
is set to
[0] Digital
and ctrl. word,
and
parameter 8-10 Control Word Profile
is set to
[1]
Profidrive profile
.
Option:
Function:
[0]
Digital input
[1]
Bus
[2]
Logic AND
[3]
*
Logic OR
8-58 Profidrive OFF3 Select
Select control of the frequency converter OFF3 selection via the
terminals (digital input) and/or via the fieldbus. This parameter is
active only when
parameter 8-01 Control Site
is set to
[0] Digital
and ctrl. word,
and
parameter 8-10 Control Word Profile
is set to
[1]
Profidrive profile
.
Option:
Function:
[0]
Digital input
[1]
Bus
[2]
Logic AND
[3]
*
Logic OR
4.9.6 8-7* Protocol SW Version
8-79 Protocol Firmware version
Range:
Function:
Size related
*
[0 - 65535 ] Firmware revision: FC is in index 0;
Modbus is in index 1; indexes 2 to 4
are reserved.
4.9.7 8-8* FC Port Diagnostics
These parameters are used for monitoring the bus
communication via the frequency converter port.
8-80 Bus Message Count
Range:
Function:
0
*
[0 - 65536 ] This parameter shows the number of valid
telegrams detected on the bus.
8-81 Bus Error Count
Range:
Function:
0
*
[0 - 65536 ] This parameter shows the number of telegrams
with faults (for example, CRC faults), detected
on the bus.
8-82 Slave Messages Rcvd
Range:
Function:
0
*
[0 - 65536 ] This parameter shows the number of valid
telegrams sent by the frequency converter to
the slave.
8-83 Slave Error Count
Range:
Function:
0
*
[0 - 65536 ] This parameter shows the number of error
telegrams, which could not be executed by the
frequency converter.
8-84 Slave Messages Sent
Range:
Function:
0
*
[0 - 65536 ] This parameter shows the number of messages
sent from the slave.
Parameter Descriptions
VLT
®
AutomationDrive FC 360
76