5.2.18 21-** Ext. Closed Loop
Par.
No. #
Parameter description
Default value
4-set-up
Change
during
operation
Conversion
index
Type
21-0* Ext. CL Autotuning
21-09 Extended PID Enable
[0] Disabled
All set-ups
TRUE
-
Uint8
21-1* Ext. CL 1 Ref./Fb.
21-11 Ext. 1 Minimum Reference
0 ExtPID1Unit
All set-ups
TRUE
-3
Int32
21-12 Ext. 1 Maximum Reference
100 ExtPID1Unit
All set-ups
TRUE
-3
Int32
21-13 Ext. 1 Reference Source
[0] No function
All set-ups
TRUE
-
Uint8
21-14 Ext. 1 Feedback Source
[0] No function
All set-ups
TRUE
-
Uint8
21-15 Ext. 1 Setpoint
0 ExtPID1Unit
All set-ups
TRUE
-3
Int32
21-17 Ext. 1 Reference [Unit]
0 ExtPID1Unit
All set-ups
TRUE
-3
Int32
21-18 Ext. 1 Feedback [Unit]
0 ExtPID1Unit
All set-ups
TRUE
-3
Int32
21-19 Ext. 1 Output [%]
0%
All set-ups
TRUE
0
Int32
Ext. CL 1 PID
21-20 Ext. 1 Normal/Inverse Control
[0] Normal
All set-ups
TRUE
-
Uint8
21-21 Ext. 1 Proportional Gain
0.01 N/A
All set-ups
TRUE
-2
Uint16
21-22 Ext. 1 Integral Time
10000 s
All set-ups
TRUE
-2
Uint32
21-23 Ext. 1 Differentiation Time
0 s
All set-ups
TRUE
-2
Uint16
21-24 Ext. 1 Dif. Gain Limit
5 N/A
All set-ups
TRUE
-1
Uint16
5.2.19 22-** Application Functions
Par. No. #
Parameter description
Default value
2-set-up
Change during
operation
Conversion
index
Type
22-4* Sleep Mode
22-40
Minimum Run Time
10 s
All set-ups
TRUE
0
Uint16
22-41
Minimum Sleep Time
10 s
All set-ups
TRUE
0
Uint16
22-43
Wake-Up Speed [Hz]
10 N/A
All set-ups
TRUE
-1
Uint16
22-44
Wake-Up Ref./FB Diff
10%
All set-ups
TRUE
0
Uint8
22-45
Setpoint Boost
0%
All set-ups
TRUE
0
Int8
22-46
Maximum Boost Time
60 s
All set-ups
TRUE
0
Uint16
22-47
Sleep Speed [Hz]
0 N/A
All set-ups
TRUE
-1
Uint16
22-6* Broken Belt Detection
22-60
Broken Belt Function
[0] Off
All set-ups
TRUE
–
Uint8
22-61
Broken Belt Torque
10%
All set-ups
TRUE
0
Uint8
22-62
Broken Belt Delay
10 s
All set-ups
TRUE
0
Uint16
5.2.20 30-** Special Features
Par. No. #
Parameter description
Default value
2-set-up
Change during
operation
Conversion
index
Type
30-2* Adv. Start Adjust
30-20
High Starting Torque Time [s]
ExpressionLimit
All set-ups
TRUE
-2
Uint16
30-21
High Starting Torque Current [%]
ExpressionLimit
All set-ups
TRUE
-1
Uint32
30-22
Locked Rotor Protection
[0] Off
All set-ups
TRUE
-
Uint8
30-23
Locked Rotor Detection Time [s]
0.10 s
All set-ups
TRUE
-2
Uint8
Parameter Lists
Programming Guide
MG06C602
Danfoss A/S © 7/2015 All rights reserved.
139