4 Parameter Descriptions
4.1 Parameters: 0-** Operation and Display
Parameters related to the fundamental functions of the
frequency converter, function of the LCP keys, and configu-
ration of the LCP display.
4.1.1 0-0* Basic Settings
0-01 Language
Option:
Function:
[0]
*
English
[10]
Chinese
0-03 Regional Settings
Option:
Function:
NOTICE
This parameter cannot be adjusted while
the motor is running.
[0]
*
Interna-
tional
Activates
parameter 1-20 Motor Power [kW]
for
setting the motor power in kW and sets the
default value of
parameter 1-23 Motor Frequency
to 50 Hz.
[1]
US
Activates
parameter 1-20 Motor Power [kW]
for
setting the motor power in hp and sets the
default value of
parameter 1-23 Motor Frequency
to 60 Hz.
0-04 Operating State at Power-up (Hand)
Option:
Function:
Selects the operating mode upon
reconnection of the frequency converter to
mains voltage after power down in
Hand On
mode.
[0]
Resume
Restarts the frequency converter, maintaining
the same start/stop settings (applied by
[Hand On/Off]) as those selected before the
power-down of the frequency converter.
[1]
*
Forced stop,
ref=old
Restarts the frequency converter with a saved
local reference after mains voltage reappears,
and after pressing [Hand On].
[2]
Forced stop,
ref=0
Resets the local reference to 0 upon
restarting the frequency converter.
0-06 GridType
Option:
Function:
Select the grid type of the supply
voltage/frequency.
NOTICE
Not all options are supported in
all power sizes.
IT grid is a supply mains, where the
neutral point of secondary side of the
transformer is not connected to
ground.
Delta is a supply mains where the
secondary part of the transformer is
delta-connected and 1 phase is
connected to ground.
[10]
380-440V/50Hz/IT-
grid
[11]
380-440V/50Hz/
Delta
[12]
380-440V/50Hz
[20]
440-480V/50Hz/IT-
grid
[21]
440-480V/50Hz/
Delta
[22]
440-480V/50Hz
[110] 380-440V/60Hz/IT-
grid
[111] 380-440V/60Hz/
Delta
[112] 380-440V/60Hz
[120] 440-480V/60Hz/IT-
grid
[121] 440-480V/60Hz/
Delta
[122] 440-480V/60Hz
0-07 Auto DC Braking
Option: Function:
Protective function against overvoltage at coast in IT
grid environment. This parameter is active only when
[1] On
is selected in this parameter, and IT-grid options
are selected in
[0]
Off This function is not active.
[1]
*
On This function is active.
Parameter Descriptions
Programming Guide
MG06C602
Danfoss A/S © 7/2015 All rights reserved.
17