5-40 Function Relay
Option:
Function:
the output goes high. Otherwise, it
goes low.
[62]
Comparator 2
See parameter group
13-1* Smart Logic
Control
. If comparator 2 in SLC is TRUE,
the output goes high. Otherwise, it
goes low.
[63]
Comparator 3
See parameter group
13-1* Smart Logic
Control
. If comparator 3 in SLC is TRUE,
the output goes high. Otherwise, it
goes low.
[64]
Comparator 4
See parameter group
13-1* Smart Logic
Control
. If comparator 4 in SLC is TRUE,
the output goes high. Otherwise, it
goes low.
[65]
Comparator 5
See parameter group
13-1* Smart Logic
Control
. If comparator 5 in SLC is TRUE,
the output goes high. Otherwise, it
goes low.
[70]
Logic rule 0
See parameter group
13-4* Logic Rules
.
If logic rule 0 in SLC is TRUE, the
output goes high. Otherwise, it goes
low.
[71]
Logic rule 1
See parameter group
13-4* Logic Rules
.
If logic rule 1 in SLC is TRUE, the
output goes high. Otherwise, it goes
low.
[72]
Logic rule 2
See parameter group
13-4* Logic Rules
.
If logic rule 2 in SLC is TRUE, the
output goes high. Otherwise, it goes
low.
[73]
Logic rule 3
See parameter group
13-4* Logic Rules
.
If logic rule 3 in SLC is TRUE, the
output goes high. Otherwise, it goes
low.
[74]
Logic rule 4
See parameter group
13-4* Logic Rules
.
If logic rule 4 in SLC is TRUE, the
output goes high. Otherwise, it goes
low.
[75]
Logic rule 5
See parameter group
13-4* Logic Rules
.
If logic rule 5 in SLC is TRUE, the
output goes high. Otherwise, it goes
low.
[80]
SL digital output
A
See
. Output A is low on
[32] Smart
Logic Action
. Output A is high on
[38]
Smart Logic Action
.
[81]
SL digital output
B
See
. Output B is low on
[32] Smart
Logic Action
. Output B is high on
[38]
Smart Logic Action
.
5-40 Function Relay
Option:
Function:
[82]
SL digital output
C
See
. Output C is low on
[32] Smart
Logic Action
. Output C is high on
[38]
Smart Logic Action
.
[83]
SL digital output
D
See
. Output D is low on
[32] Smart
Logic Action
. Output D is high on
[38]
Smart Logic Action
.
[160] No alarm
The output is high when no alarm is
present.
[161] Running reverse
The output is high when the frequency
converter is running counterclockwise
(the logical product of the status bits
Running
AND
Reverse
).
[165] Local ref active
[166] Remote ref active
[167] Start command
activ
The output is high when there is an
active start command, and no stop
command is active.
[168] Drive in hand
mode
The output is high when the frequency
converter is in
Hand On
mode.
[169] Drive in auto
mode
The output is high when the frequency
converter is in
Auto On
mode.
[170] Homing
Completed
The homing operation is completed.
This option is only effective when
parameter 37-00 Application Mode
is set
to
[2] Position Control
.
[171] Target Position
Reached
The target position is reached. This
option is only effective when
parameter 37-00 Application Mode
is set
to
[2] Position Control
.
[172] Position Control
Fault
A fault occurred in the positioning
process. Refer to
for details about the
fault. This option is only effective when
parameter 37-00 Application Mode
is set
to
[2] Position Control
.
[173] Position Mech
Brake
Selects mechanical control for
positioning. This option is only
effective when
parameter 37-00 Application Mode
is set
to
[2] Position Control
.
[175] Running on
tension
Indicates whether tension PID control
is active (
on
) or inactive (
off
). This
option is only effective when
parameter 37-00 Application Mode
is set
to
[1] Center winder
.
[176] Ready to run
The center winder control is ready to
run. This option is only effective when
Parameter Descriptions
Programming Guide
MG06C602
Danfoss A/S © 7/2015 All rights reserved.
57
4