Refer to section 5.1 to adjust the RH set point
and refer to the Set-up menu to enable this
RH compensation method (
“Use heater RH
compensation”
parameter in section 4.4).
Select:
1.
Main menu
* On / Off Settings
*A password may be required to access this menu
(see section 4.2.1).
Use the arrow keys to scroll down and select
2.
any heating output.
Heat
Compens
On/Off Settings
...
Heat 1
Heat 1 hi
Heat 2
Heat 2 hi
Heat 3
Heat 3 hi
...
On Off
Mode Fan shutoff
Items
To modify use
-
Set Point : 75.0
73.0
74.5
72.0 74.0 Heating
73.0 74.5 Heating
72.0 74.0 Heating
73.0 74.5 Heating
72.0 74.0 Heating
...
Select the
3.
“Heat Compens”
tab with the menu
selectors.
* This tab is accessible if the Use heater RH
compensation” option is enabled in the Set-up menu
(see section 4.4).
Heater RH Compensation
To modify use
-
Min On
Cycle
Max On
0:15 M:S
5:00 M:S
0:45 M:S
Set the following parameters:
4.
Heat Min/Max On —
Set the minimum and
maximum
“On Times”
of the RH heat timer.
Cycle Time —
Set the
“Cycle Time”
of the RH
heat timer.
RH Compensation with
12.3.
the Cooling Outputs
Low RH Compensation:
The controller can
compensate for low humidity levels by ac-
tivating the cooling outputs in timer mode.
The cooling output start being used for this
purpose when the RH level falls below a user-
defined level.
High RH Compensation:
The controller can
compensate for high humidity levels by
stopping all cooling outputs. When this RH
compensation mode is used, all cooling out-
puts stop when the RH level reaches the RH
set point. Refer to section 5.1 to adjust the
RH set point.
Select:
1.
Main menu
* On / Off Settings
*A password may be required to access this menu
(see section 4.2.1).
Use the arrow keys to scroll down and select
2.
any cooling output.
* These outputs are available if
they have previously been enabled in the Set-up menu
(see section 4.4).
Cool 1
Settings
On/Off Settings
...
Cool 1
Cool 2
Cool 3
Cool 4
Cool 5
Cool 6
...
On Off
Mode Fan shutoff
Items
To modify use
-
Set Point : 75.0
...
85.0
84.5
85.0 84.5 Cooling
85.0 84.5 Cooling
85.0 84.5 Cooling
85.0 84.5 Cooling
85.0 84.5 Cooling
...
Select the
3.
“Cool #x Settings”
tab with the menu
selectors.
Cool 1 Settings
To modify use
-
Cool shutoff
On Time
Low RH
Off Time
85
0:30 M:S
40
2:00 M:S
Set the following parameters. Note that
4.
the RH compensation settings are common
to all cooling outputs:
Cool Shutoff —
Set the humidity level above
which the cooling outputs must stop being
used. *
This parameter is accessible if the “RH
shutoff cooling” option is enabled in the Set-up menu
(see section 4.4).
Lo RH—
Set the humidity level below which
the cooling outputs must start running in
timer mode. *
This parameter is accessible if the
“Activate cooling on low RH” option is enabled in
the Set-up menu (see section 4.4).
On & Off Times —
Set the
“On
&
Off Times”
of
the Lo RH Cooling timer. *
These parameters are
accessible if the “Activate cooling on low RH” option
is enabled in the Set-up menu (see section 4.4).