background image

6

PRO-VISION   rev.04

PRO-VISION

Main Features

1.4. 

Easy-to-Use  Controller  —

  With  its  conve-

nient  menu selectors and its large graphic 

LCD screen, the PRO-VISION is certainly the 

most easy-to-use temperature controller on 

the market. 

5  Controller  Programs  — 

The  controller  al-

lows using 5 different programs to control the 

room temperature. It is thus possible to acti-

vate a specific program that uses particular 

temperature  settings according to the animal 

age for instance.

32  Indoor  Temperature  Sensors  — 

Up  to 

32 temperature sensors can be connected to 

the controller to obtain an accurate reading 

of the average room temperature and a faster 

reaction time. The controller comes with 8 

basic temperature inputs and 24 additional 

inputs can be added with the optional exten-

sion cards.

Minimum  Ventilation  Cycle  — 

When  ven-

tilation  is  not  required  to  reduce  the  room 

temperature, fan outputs can run either con-

tinuously or intermittently to reduce humidity 

levels and supply oxygen to the room.

Recuperation  of  the  Warm  Attic  Air  —

  In 

order to make energy savings, the controller 

can extract the warm air from the attic and 

send it back into the room.

Tunnel  Ventilation  — 

When  the  room  tem-

perature  rises,  tunnel  ventilation  reduces 

the  actual  temperature  perceived  by  the 

animals.

Natural  Ventilation  — 

This  is  a  ventilation 

mode  that  uses  existing  air  currents  and 

natural convection to move and distribute air 

through the building.

Humidity Control — 

The control offers many 

ways to compensate for high or low humid-

ity levels. 

Control  of  the  Air  Inlet  Movement  — 

The 

movement  of  the  air  inlets  (sidewall  vents 

or  tunnel  inlets)  can  be  coordinated  with 

the  operation  of  the  fans  or  according  to 

the pressure level. This allows the inlets to 

be adjusted correctly, without the influence 

of uncontrollable factors such as wind or air 

from adjoining rooms.

Egg  Room  — 

In  addition  to  controlling  the 

ambient temperature in the house, the PRO-

VISION  can  control  the  temperature  and 

humidity conditions in an egg room. It can 

also  keeps  a  tally  of  the  number  of  eggs 

produced each day.

Operation  Cost  Monitoring  —

  The  control-

ler  can  monitor  the  amperage  draw  of  the 

outputs  and  give  you  daily  reports  of  the 

operation costs.

History Menus — 

The history menus allow 

monitoring the sensor readings and verify the 

run time of some outputs. Below is a list of 

all available histories menus:

Minimum and maximum sensor readings: 

  Ambient temperature ................ 400 days
  Inside temperature sensors ............ 7 days
  Outside temperature sensor ....... 400 days
  Relative humidity sensor ........... 400 days

2.  MOUNTING INSTRUC-

TIONS

Installing the Controller 

2.1. 

on the Wall

Fasten the two metal brackets on the mount-
ing holes located behind the controller using 
four screws. Then, mount the enclosure on 
the  wall  using  four  other  screws.  Leave  a 
clearance of at least 16” to the left of the 
enclosure to allow the cover to be removed 
for maintenance. 

  Static pressure sensor ............... 400 days
Heater run time .......................... 400 days
Feeder run time .......................... 400 days
Water consumption ..................... 400 days
Mortality ................................... 400 days

Alarm Management — 

The controller provides 

alarms for high-low temperatures, defective 
sensors and other system failures. It keeps in 
memory the 75 latest alarm conditions.

Password Protection — 

Different passwords 

levels  can  be  enabled  to  restrict  access  to 
some menus of the controller.

Backup Battery — 

A backup battery allows 

the  unit  to  keep  time  in  case  of  a  power 
failure.

USB  Connector 

—  Controller  backups  and 

updates can be made easily with a standard 
USB memory card. 

Overload and Over-voltage Protection — 

Re-

settable  fuses  are  provided  at  low-voltage 
inputs of the controller to protect its circuitry 
in the case of an overload or over-voltage.

Computer Control — 

The controller can be 

connected  to  a  computer,  thus  making  it 
possible  to  centralize  the  management  of 
information and diversify control strategies.

Test  Mode  — 

A  test  mode  allows  simulat-

ing  temperature changes and verifying the 
controller‘s performances.

Connections

2.2. 

2.2.1.  Main Wiring 

Refer to the wiring diagram enclosed with this 
user’s manual to connect the controller. Drill 
holes at the bottom of the enclosure to pass 
the wires and install watertight connectors to 
prevent water from entering in the enclosure. 
Do not make any holes at the side and top of 
the enclosure.

All  wiring  must  be  done  by  an  autho-
rized electrician and must comply with 
applicable codes, laws and regulations. 
Make sure power is off before doing any 
wiring  to  avoid  electrical  shocks  and 
equipment damage.

Содержание PRO-VISION

Страница 1: ...7 DEL 2 5 8 0 3 6 9 AM PM ENTER MAIN MENU BACK M 890 00515 rev 04 REV 04 PRO VISION Temperature controller User s Manual Main Menu Current conditions Set Point Minimum ventilation On Off Settings Inle...

Страница 2: ...if this product is used in a manner not specified by the manufacturer Every effort has been made to ensure that this manual is complete accurate and up to date The information con tained in it is howe...

Страница 3: ...re RH Set Points 16 5 2 Set Point Ramp 16 6 VENTILATION COOLING 17 6 1 Overview of the Ventilation Concepts 17 6 2 Minimum Ventilation 18 6 2 1 Minimum Ventilation Timer 18 6 2 2 Min Ventilation Timer...

Страница 4: ...eder Alarm 38 13 2 5 Amperage Draw Alarm 38 13 2 6 0 10V Output Error 38 14 MONITORING FUNCTIONS 39 14 1 Current Conditions 39 14 1 1 Current Condition Screen Saver 39 14 1 2 Current Input Output Stat...

Страница 5: ...rload or over voltage we recommend installing an additional protection device on the controller s supply circuit The room temperature where the controller is located must always remain between 32 F an...

Страница 6: ...ge draw of the outputs and give you daily reports of the operation costs History Menus The history menus allow monitoring the sensor readings and verify the run time of some outputs Below is a list of...

Страница 7: ...tons Digital Keypad AM PM Button Delete Do not run sensor cables next to other power cables When crossing over other cables cross at 90 Defective sensors An alarm is generated when a defective sensor...

Страница 8: ...le disable this protection see section 4 4 Entering a Password 4 2 1 If the password protection is used the con troller will prompt for a password each time a user that does not have the proper privil...

Страница 9: ...0 00 No 10000 On 10000 10000 Program 1 0 No Set the following parameters 2 Program Activate the desired controller program Only the programs that are enabled in the Set up menu can be used see section...

Страница 10: ...an an emometer is connected to the controller Use ammonia sensor Select Yes if an am monia sensor is connected to the controller Use water flush Select Yes to use the water line flush Refer to chapte...

Страница 11: ...the fans in minimum ventilation when temperature is suitable in the attic Select Yes to enable this compensation function refer to section 6 5 for further information on this function This parameter...

Страница 12: ...5 60 0 63 5 60 0 63 5 When an output is selected the controller displays a sensor assignment tab at the right hand side of the screen the tab is associated with the chosen output If the output oper at...

Страница 13: ...bration settings are common to all programs of the controller Use the key to enter a negative offset Temperature indoor outdoor The reading of the inside and outside temperature sensors can be adjuste...

Страница 14: ...is menu see sec 4 2 1 This menu is accessible if a current sensor is enabled in the Set up menu see section 4 4 Relay current sensor assignment To modify use 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17...

Страница 15: ...t automati cally ends after 15 minutes of inactivity or if the user deactivates it manually Select 1 Main menu Set up Test Mode A complete access password may be required to access this menu see sec 4...

Страница 16: ...pensation functions to lower it down see chapter 12 Set the relative humidity set point to the desired value This parameter is accessible if the controller is used in a broiler or turkey facility Refe...

Страница 17: ...lation This transition is optional Minimum Vent opt Lateral Mode opt Tunnel Mode opt Natural Mode ON T of the first lateral fan Startup of the first natural ventilation curtain see sec 6 5 3 Startup o...

Страница 18: ...tically adjust the On Time portion of the minimum ventilation timer with time The minimum ventilation ramp is composed of 12 steps and each step associates an On Time with an animal age Once the ramp...

Страница 19: ...ns stop When the fans stop both vents close and stay closed until the beginning of the next cycle b Without the attic compensation If the attic vent is used but the attic compensation function is disa...

Страница 20: ...ecreasing gradually in a linear fash ion as the room temperature falls The On Time finally stops being compensated when the room temperature reaches the Attic start comp at value Select 1 Main menu In...

Страница 21: ...ation A fan output that is labeled Timer runs according to a timer in minimum ventilation and runs continuously when the room tem perature reaches its On Temperature Close Attic The controller can clo...

Страница 22: ...limits separately for hot and cold weather conditions This param eter is accessible if the attic compensation function is enabled in the Set up menu see section 4 4 Wind Delay When the pressure level...

Страница 23: ...the start up of tunnel ventilation the natural ventilation curtains close completely and the tunnel inlet opens in the meanwhile When the natural ventilation curtains are totally closed the tunnel in...

Страница 24: ...tunnel inlet from opening when the animals are too young or when it is too cold outside for instance If the tunnel mode is on standby and the room temperature is suitable for tunnel ventilation the co...

Страница 25: ...enable the tunnel inlets and to choose their operating mode If 2 tunnel inlets are used they both follows the same movements However both tunnel inlets do not start being used at the same time The 1s...

Страница 26: ...on 4 4 Pre opening 2 Specify how much time is required to pre open the tunnel inlet at the startup of tunnel ventilation when the transi tion from sidewall to tunnel ventilation is over The controller...

Страница 27: ...Select the 4 Settings tab that is associated with the chosen cooling output with the menu selectors Set the following parameters separately 5 for each cooling output in use Cool 1 Settings Max Run T C...

Страница 28: ...aters are defined with respect to the temperature set point and with respect to heater 1 if the set point changes the on off temperatures of all heaters will be adjusted by the same amount and if the...

Страница 29: ...Duration Time Light Cycles used to prepare the house before letting the animals in Lights 24hr Select Yes for the lights to stay lit all day long select No to use the light cycles Use Peaks Select Yes...

Страница 30: ...iagrams show both possibilities Time Time Output Status Cycle Cycle Output Status On Start Time e g 8h30AM Start Time e g 8h30AM Time Clock Start Run Mode Time Clock Start Stop Mode Run Time e g 30m 1...

Страница 31: ...shown below only if the Breeder facility is enabled in the Set up menu see section 4 4 Time clock Start Start Run Time Run Time Display 6 00 am 6 00 am 0 00 00 0 00 00 Clock 1 Skip day No Sun Mon Tue...

Страница 32: ...m 12 00 am Program1 2 0 10 H M 4 12 00 am 12 00 am Start Mon Duration Interval Duration Interval Duration Interval Duration Output 1 starts flushing Output 2 starts flushing Output 3 starts flushing O...

Страница 33: ...troller is located breeder broiler or turkey When the egg room is used the PRO VISION also keeps a tally of the number of eggs pro duced each day the egg tally includes the daily count of produced cra...

Страница 34: ...As the RH level rises the controller increases the On Time portion of the minimum ventilation timer to compensate for the change The maximum compensated On Time is reached when the RH level is 10 abov...

Страница 35: ...midity levels by stopping all cooling outputs When this RH compensation mode is used all cooling out puts stop when the RH level reaches the RH set point Refer to section 5 1 to adjust the RH set poin...

Страница 36: ...his means an alarm is declared when the room temperature reaches Outside Temperature High Alarm Offset the offset being the difference between the high alarm temperature setting and the set point A th...

Страница 37: ...ure relay can be used to activate additional fans for instance Refer to section 4 7 to enable this type or relay Low Static Pressure Alarm in Minimum Ventilation In minimum ventilation the con troller...

Страница 38: ...to specify what relays are using this type of sensor Amp draw alarm Item Minimum Maximum Heaters 1 0A 5 0A Fan 1 0A 5 0A Tun Fan 1 0A 5 0A Cooling 1 0A 5 0A Stir 1 0A 5 0A Time clock 1 0A 5 0A Light 1...

Страница 39: ...ay s heater run time Min Temp Avr temp Max Temp Age 75 2 F 77 5 F 80 0 F 5 Out Temp Humidity S P Water 1 78 0 F 75 0 06 WC 7 gal Water 2 Ammonia Wind spd 3 gal 0ppm 0ft min Hi Hi Hi Hi Hi Hi 75 3 75 1...

Страница 40: ...s at the beginning of a flock You must then update the animal count when mortality occurs Select 1 Main menu Start Flock A complete access password may be required to access this menu see section 4 2...

Страница 41: ...plete access password may be required to access this menu see section 4 2 1 This tab is accessible if the Breeder application is enabled in the Set up menu see section 4 4 Egg count To modify use Coun...

Страница 42: ...t affecting your parameter settings Update settings Press this tab in order to load the parameter settings of the selected file into your PRO VISION controller This transfer will affect the parameter...

Страница 43: ...15 to 50 C Ambient relative humidity Max 95 Pollution degree 2 Altitude Up to 2000m Outputs 14Vdc outputs 14 Vdc 10 regulated 350 mA max 0 10V outputs 1 2 0 10Vdc 30mA source max Precision on 0 10V o...

Страница 44: ...ius units 10 Clean mode Activate deactivate 15 Clean mode T set point 16 Low T alarms in clean mode Activating the alarm condition 15 Alarm limit 36 Operation settings 14 Clock Setting the time and da...

Страница 45: ...Fans Operation settings 21 22 Overview of the ventilation concepts 17 LCD screen 7 Diagnostic 42 LED Alarm 7 Lights Lights on the 0 10V output 0 10V Wiring 7 Activation 11 Current intensity 39 Diagnos...

Страница 46: ...nts Attic vent S P set points 22 Sidewall vent S P set points 22 Tunnel inlet S P set points 26 Stir fans Activation 11 Amp draw Operation cost See Amperage draw Operation settings 27 Output status 39...

Страница 47: ...Ventilation concepts 17 Vents See Sidewall vent Attic vents or Tunnel inlet Version software 15 Voltage See Amperage draw Volume keypad 9 W Water line flush outputs Activation 10 Amp draw Operation c...

Страница 48: ...______________________ E mail ____________________________________________________________ ES HOJAS DE TRABAJO CLIENTE Nombre ____________________________________________________________ Direcci n ___...

Страница 49: ...r 1 4 Cooling 1 6 Clock 1 8 Flush output 1 8 Stir fan Lights Backup relay Low SP SV C sidewall vents close SV O sidewall vents open AV C attic vents close AV O attic vents open NT1 C Natural curtain 1...

Страница 50: ...n Funci n de rel Prog 1 Prog 2 Prog 3 Prog 4 Prog 5 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104...

Страница 51: ...Plantilla del men de instalaci n Par metros Campo de valores Su par metro para el programa n 1 2 3 4 5 Contraste 10 100 Com n en todos los programas Volumen teclado 0 100 Com n en todos los programas...

Страница 52: ...o all programs Par metros Campo de valores Su par metro para el programa n 1 2 3 4 5 Activar enfriamiento si HR baja S No N de alimentadores 1 4 Utilizar circuladores de aire S No Cicrulador seg n Tem...

Страница 53: ...play All w o heat run time w o heat run time T sensors Common to all programs Par metros Campo de valores Su par metro para el programa n 1 2 3 4 5 Tensi n Circul 108 V 120 V o 240 V Com n en todos lo...

Страница 54: ...PRO VISION NOTES NOTAS...

Страница 55: ...PRO VISION NOTES NOTAS...

Отзывы: