22
PRO-VISION rev.04
PRO-VISION
Select:
1.
Main menu
* Inlets / Vents
* This menu is accessible if at least 1 inlet is enabled
in the Set-up menu (see section 4.4). A password may
also be required to access it (see section 4.2.1).
Set the following parameters:
2.
Sidewall Vents Lo/Hi Pressure Limits —
Set
the static pressure level below/above which
the vents must close/open. If an outside
temperature sensor is used, set these limits
separately for hot and cold weather condi-
tions.*
This parameter is accessible if the sidewall
vent is enabled in the Set-up menu (see section 4.4).
Opening of the Sidewall & Attic Vents
in Lateral Ventilation
Time
Static
Pressure
The vents open
The vents close
Sidewall
Lo pressure
limits*
Sidewall
Hi pressure
limits*
The vents
starts closing
after the Wind
Delay has
elapsed.
The vents
start opening
after the Wind
Delay has
elapsed.
The vents stop
closing
The vents stop
opening
Wind
Delay
Wind
Delay
The vents do not move
*The Hi and Lo pressure limits can automatically be adjusted according to the outside temperature
Attic Vents Lo/Hi Pressure Limits —
Set the
static pressure level below/above which the
attic vent must close/open when the attic
compensation is on. If an outside temperature
sensor is used, set these limits separately for
hot and cold weather conditions.*
This param-
eter is accessible if the attic compensation function is
enabled in the Set-up menu (see section 4.4).
Wind Delay —
When the pressure level gets
out of range, the air inlets wait for the end
of the
“Wind Delay”
before moving; they only
move if the high or low pressure condition is
valid all along this delay. This way, the inlets
do not move if a wind draft causes fleeting
changes in the pressure level. Set the “
Wind
Delay”
to the desired value. *
Note that this
parameter is common to all air inlets (sidewall vent,
attic vent and tunnel inlets).
Pre-opening Vents —
Specify how much time
is required to pre-open the sidewall & attic
vents before activating the fans in minimum
ventilation. Refer to section 6.2.4 for further
information on this delay. *
This parameter is
accessible if the pre-opening is not set automatically
by the controller. Refer to the Set-up menu in section
4.4 to enable/disable the automatic pre-opening
function.
Outside T° Hot & Cold —
Specify the out-
door temperature at which hot & cold static
pressure limits are used. *
These parameters are
accessible if an outside temperature sensor is enabled
in the Set-up menu (see section 4.4).
Inlets / Vents
To Modify Press
-
Attic
Hot SP Cold SP
Vents Lo
0.03
Hi
0.05
Lo
0.03
Hi
0.05
Sidewall Hot SP Cold SP
Vents Lo
0.03
Hi
0.05
Lo
0.03
Hi
0.05
Wind delay
0:30M:S
Outside T°
Cold
Outside T°
Hot
Pre-opening
Vents
5.0°F
45.0°F
15sec