PRO-VISION   rev.04

PRO-VISION

put a special attribute. Set the mode of each 
tunnel fan output as follows (set the mode to 
“—” if nothing applies to an output).

Timer  —

  The 

“Timer”

  label  identifies  a 

tunnel fan output that is used in minimum 
ventilation. A tunnel fan that has this label 
runs according to a timer in minimum venti-
lation and runs continuously when the room 
temperature reaches its 

“On Temperature”

.

Start tunnel —

 The 

“Start tunnel”

 label indi-

cates  the  moment  at  which  the  transition 
from lateral to tunnel ventilation begins: the 
first  tunnel  inlet  starts  being  used  at  the 
start-up of that tunnel fan and the sidewall 
vent keeps being used. 

Close  sidewall  —

  The 

“Close sidewall” 

label 

indicates the moment at which lateral venti-
lation ends. The sidewall vent closes at the 
startup of the chosen tunnel fan and the tun-
nel ventilation mode becomes fully effective 
at that moment.  

St.tun,clo.side —

 The 

“Start tunnel, close side-

wall”

  label  indicates  the  moment  at  which 

the controller switches from lateral to tun-
nel ventilation. With this option, there is no 
gradual transition made from one ventilation 
mode to the other. The sidewall vents close 
and the tunnel inlet start being used at the 
startup of the chosen tunnel fan.

Start  tunnel  2  —

  The  second  tunnel  inlet 

starts being used at the startup of the se-
lected tunnel fan output.

Fan Shutoff Column: 

Fan  Shutoff  —

  The  controller  can  disable 

some  lateral  fans  at  the  startup  of  chosen 
tunnel  fan  outputs.  Select  the  moment  at 
which  each  lateral  fan  must  stop  (if  appli-
cable). Note that when a fan is stopped, it 

will not restart until the controller re-enters 
in lateral ventilation. 

If you want the selected fan to run when 

4. 
a  particular  time  clock  output  is  on,  select 
the 

“Follow Clock”

 tab with the menu selec-

tors  and  then  set  parameters  below. 

*This 

tab is only accessible if the controller is used in a 

breeder facility.

Tunnel fan 1 follow clock

Follow clock

Low stop T°

Stat.Pressure

2

73.0

Follow clock —

 Select during the operation 

of  which  time  clock  output  you  want  the 
selected tunnel fan to run. 

Low stop T° —

 The selected tunnel fan will 

stop  following  the  time  clock  output  if  the 
room temperature gets too low. Set this se-
curity limit to the desired value.

Tunnel Inlets

6.5.4. 

The  controller  can  control  the  opening  of 
2 tunnel inlets. These inlets either operate as 
a function of the static pressure level or as a 
function of temperature. Refer to the Set-up 
menu in section 4.4 to enable the tunnel inlets 
and to choose their operating mode. 

If 2 tunnel inlets are used, they both follows 
the same movements. However, both tunnel 
inlets do not start being used at the same time. 
The 1

st

 inlet starts being used at the beginning 

of tunnel ventilation and the 2

nd

 inlet starts at 

the startup of another user-defined tunnel fan 
output. Refer to the previous section of this 
manual  to  set  the  moment  at  which  the  2

nd

 

tunnel inlet starts being used.

 

6.5.4.1. 

Temperature-based Tun-

nel Inlet 

When using temperature-based tunnel inlets, 
the user must associate an actuator position 
with  the  startup  of  each  tunnel  fan.  This 
way, when a fan/tunnel fan starts, the inlet 
opens  accordingly.  The  tunnel  inlet  starts 
opening this way at the beginning of tunnel 
ventilation. The graph below shows how the 
tunnel inlet opens. Refer to Set-up menu in 
section  4.4  to  enable  a  temperature-based 
tunnel inlet.

Pre-opening of the Tunnel Inlet: 

At the be-

ginning  of  tunnel  ventilation,  the  controller 
waits  for  the  tunnel  inlet  to  reach  half  of 
its  programmed  position  before  activating 
the  fans  (or  waits  30  seconds,  whichever 
is shorter). 

1. Select:

     Main menu

  *  Inlets / Vents

* * Tunnel Opening

 * This menu is accessible if at least 1 inlet is enabled 

in the Set-up menu (see section 4.4). A password may 

also be required to access it (see section 4.2.1).

*  *  This  menu  is  accessible  if  the  tunnel  inlet’s 

operating mode is set to “T°” in the Set-up menu 

(see section 4.4).

Tunnel Opening

Tun 1
Tun 2
Tun 3
Tun 4
Tun 5
Tun 6

...

Total open time

0%
5%

10%
15%
20%
25%

...

5:00 M:S

   To modify use 

 

   

 - 

Set the following parameters:

2. 

Tun #x Opening —

 Associate a tunnel inlet 

opening (in %) with the startup of each tun-
nel fan. 

If a tunnel fan is used in lateral ventila-
tion, set its tunnel inlet opening to 0% if 
you don’t want the tunnel inlet to open 
in lateral ventilation!

Total opening time —

 Specify the exact time 

that is required to reach the actuator’s maxi-
mum limit switch. The controller will limit the 
opening of the inlet according to this value. 
*

 This parameter is common to all programs.

 

6.5.4.2. 

Pressure-based 

Tunnel Inlets

Opening of the Tunnel Inlet: 

If  the  tunnel  inlets  are  controlled  by  static 
pressure, the first inlet start moving accord-
ing to the fluctuations in the pressure level 
when the controller enters in tunnel ventila-
tion. It open when the pressure level exceeds 
the high pressure limit and closes when the 
pressure level gets lower than the low pres-

Follow

Clock

On/Off Settings

...

Tun 1
Tun 2
Tun 3
Tun 4
Tun 5
...

 On   Off 

    Mode       Fan shutoff

 Items

  

To modify use 

 

   

 - 

 

      Set Point : 75.0

  ...

 

 

 82.0

  80.0  

 80.0  79.0 Start tunnel 2
 81.0  80.0 Close sidewall 3 4 5
 82.0  81.0      - 

-

 83.0  82.0 Start 

tunnel 

2   

  ... 

Содержание PRO-VISION

Страница 1: ...7 DEL 2 5 8 0 3 6 9 AM PM ENTER MAIN MENU BACK M 890 00515 rev 04 REV 04 PRO VISION Temperature controller User s Manual Main Menu Current conditions Set Point Minimum ventilation On Off Settings Inle...

Страница 2: ...if this product is used in a manner not specified by the manufacturer Every effort has been made to ensure that this manual is complete accurate and up to date The information con tained in it is howe...

Страница 3: ...re RH Set Points 16 5 2 Set Point Ramp 16 6 VENTILATION COOLING 17 6 1 Overview of the Ventilation Concepts 17 6 2 Minimum Ventilation 18 6 2 1 Minimum Ventilation Timer 18 6 2 2 Min Ventilation Timer...

Страница 4: ...eder Alarm 38 13 2 5 Amperage Draw Alarm 38 13 2 6 0 10V Output Error 38 14 MONITORING FUNCTIONS 39 14 1 Current Conditions 39 14 1 1 Current Condition Screen Saver 39 14 1 2 Current Input Output Stat...

Страница 5: ...rload or over voltage we recommend installing an additional protection device on the controller s supply circuit The room temperature where the controller is located must always remain between 32 F an...

Страница 6: ...ge draw of the outputs and give you daily reports of the operation costs History Menus The history menus allow monitoring the sensor readings and verify the run time of some outputs Below is a list of...

Страница 7: ...tons Digital Keypad AM PM Button Delete Do not run sensor cables next to other power cables When crossing over other cables cross at 90 Defective sensors An alarm is generated when a defective sensor...

Страница 8: ...le disable this protection see section 4 4 Entering a Password 4 2 1 If the password protection is used the con troller will prompt for a password each time a user that does not have the proper privil...

Страница 9: ...0 00 No 10000 On 10000 10000 Program 1 0 No Set the following parameters 2 Program Activate the desired controller program Only the programs that are enabled in the Set up menu can be used see section...

Страница 10: ...an an emometer is connected to the controller Use ammonia sensor Select Yes if an am monia sensor is connected to the controller Use water flush Select Yes to use the water line flush Refer to chapte...

Страница 11: ...the fans in minimum ventilation when temperature is suitable in the attic Select Yes to enable this compensation function refer to section 6 5 for further information on this function This parameter...

Страница 12: ...5 60 0 63 5 60 0 63 5 When an output is selected the controller displays a sensor assignment tab at the right hand side of the screen the tab is associated with the chosen output If the output oper at...

Страница 13: ...bration settings are common to all programs of the controller Use the key to enter a negative offset Temperature indoor outdoor The reading of the inside and outside temperature sensors can be adjuste...

Страница 14: ...is menu see sec 4 2 1 This menu is accessible if a current sensor is enabled in the Set up menu see section 4 4 Relay current sensor assignment To modify use 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17...

Страница 15: ...t automati cally ends after 15 minutes of inactivity or if the user deactivates it manually Select 1 Main menu Set up Test Mode A complete access password may be required to access this menu see sec 4...

Страница 16: ...pensation functions to lower it down see chapter 12 Set the relative humidity set point to the desired value This parameter is accessible if the controller is used in a broiler or turkey facility Refe...

Страница 17: ...lation This transition is optional Minimum Vent opt Lateral Mode opt Tunnel Mode opt Natural Mode ON T of the first lateral fan Startup of the first natural ventilation curtain see sec 6 5 3 Startup o...

Страница 18: ...tically adjust the On Time portion of the minimum ventilation timer with time The minimum ventilation ramp is composed of 12 steps and each step associates an On Time with an animal age Once the ramp...

Страница 19: ...ns stop When the fans stop both vents close and stay closed until the beginning of the next cycle b Without the attic compensation If the attic vent is used but the attic compensation function is disa...

Страница 20: ...ecreasing gradually in a linear fash ion as the room temperature falls The On Time finally stops being compensated when the room temperature reaches the Attic start comp at value Select 1 Main menu In...

Страница 21: ...ation A fan output that is labeled Timer runs according to a timer in minimum ventilation and runs continuously when the room tem perature reaches its On Temperature Close Attic The controller can clo...

Страница 22: ...limits separately for hot and cold weather conditions This param eter is accessible if the attic compensation function is enabled in the Set up menu see section 4 4 Wind Delay When the pressure level...

Страница 23: ...the start up of tunnel ventilation the natural ventilation curtains close completely and the tunnel inlet opens in the meanwhile When the natural ventilation curtains are totally closed the tunnel in...

Страница 24: ...tunnel inlet from opening when the animals are too young or when it is too cold outside for instance If the tunnel mode is on standby and the room temperature is suitable for tunnel ventilation the co...

Страница 25: ...enable the tunnel inlets and to choose their operating mode If 2 tunnel inlets are used they both follows the same movements However both tunnel inlets do not start being used at the same time The 1s...

Страница 26: ...on 4 4 Pre opening 2 Specify how much time is required to pre open the tunnel inlet at the startup of tunnel ventilation when the transi tion from sidewall to tunnel ventilation is over The controller...

Страница 27: ...Select the 4 Settings tab that is associated with the chosen cooling output with the menu selectors Set the following parameters separately 5 for each cooling output in use Cool 1 Settings Max Run T C...

Страница 28: ...aters are defined with respect to the temperature set point and with respect to heater 1 if the set point changes the on off temperatures of all heaters will be adjusted by the same amount and if the...

Страница 29: ...Duration Time Light Cycles used to prepare the house before letting the animals in Lights 24hr Select Yes for the lights to stay lit all day long select No to use the light cycles Use Peaks Select Yes...

Страница 30: ...iagrams show both possibilities Time Time Output Status Cycle Cycle Output Status On Start Time e g 8h30AM Start Time e g 8h30AM Time Clock Start Run Mode Time Clock Start Stop Mode Run Time e g 30m 1...

Страница 31: ...shown below only if the Breeder facility is enabled in the Set up menu see section 4 4 Time clock Start Start Run Time Run Time Display 6 00 am 6 00 am 0 00 00 0 00 00 Clock 1 Skip day No Sun Mon Tue...

Страница 32: ...m 12 00 am Program1 2 0 10 H M 4 12 00 am 12 00 am Start Mon Duration Interval Duration Interval Duration Interval Duration Output 1 starts flushing Output 2 starts flushing Output 3 starts flushing O...

Страница 33: ...troller is located breeder broiler or turkey When the egg room is used the PRO VISION also keeps a tally of the number of eggs pro duced each day the egg tally includes the daily count of produced cra...

Страница 34: ...As the RH level rises the controller increases the On Time portion of the minimum ventilation timer to compensate for the change The maximum compensated On Time is reached when the RH level is 10 abov...

Страница 35: ...midity levels by stopping all cooling outputs When this RH compensation mode is used all cooling out puts stop when the RH level reaches the RH set point Refer to section 5 1 to adjust the RH set poin...

Страница 36: ...his means an alarm is declared when the room temperature reaches Outside Temperature High Alarm Offset the offset being the difference between the high alarm temperature setting and the set point A th...

Страница 37: ...ure relay can be used to activate additional fans for instance Refer to section 4 7 to enable this type or relay Low Static Pressure Alarm in Minimum Ventilation In minimum ventilation the con troller...

Страница 38: ...to specify what relays are using this type of sensor Amp draw alarm Item Minimum Maximum Heaters 1 0A 5 0A Fan 1 0A 5 0A Tun Fan 1 0A 5 0A Cooling 1 0A 5 0A Stir 1 0A 5 0A Time clock 1 0A 5 0A Light 1...

Страница 39: ...ay s heater run time Min Temp Avr temp Max Temp Age 75 2 F 77 5 F 80 0 F 5 Out Temp Humidity S P Water 1 78 0 F 75 0 06 WC 7 gal Water 2 Ammonia Wind spd 3 gal 0ppm 0ft min Hi Hi Hi Hi Hi Hi 75 3 75 1...

Страница 40: ...s at the beginning of a flock You must then update the animal count when mortality occurs Select 1 Main menu Start Flock A complete access password may be required to access this menu see section 4 2...

Страница 41: ...plete access password may be required to access this menu see section 4 2 1 This tab is accessible if the Breeder application is enabled in the Set up menu see section 4 4 Egg count To modify use Coun...

Страница 42: ...t affecting your parameter settings Update settings Press this tab in order to load the parameter settings of the selected file into your PRO VISION controller This transfer will affect the parameter...

Страница 43: ...15 to 50 C Ambient relative humidity Max 95 Pollution degree 2 Altitude Up to 2000m Outputs 14Vdc outputs 14 Vdc 10 regulated 350 mA max 0 10V outputs 1 2 0 10Vdc 30mA source max Precision on 0 10V o...

Страница 44: ...ius units 10 Clean mode Activate deactivate 15 Clean mode T set point 16 Low T alarms in clean mode Activating the alarm condition 15 Alarm limit 36 Operation settings 14 Clock Setting the time and da...

Страница 45: ...Fans Operation settings 21 22 Overview of the ventilation concepts 17 LCD screen 7 Diagnostic 42 LED Alarm 7 Lights Lights on the 0 10V output 0 10V Wiring 7 Activation 11 Current intensity 39 Diagnos...

Страница 46: ...nts Attic vent S P set points 22 Sidewall vent S P set points 22 Tunnel inlet S P set points 26 Stir fans Activation 11 Amp draw Operation cost See Amperage draw Operation settings 27 Output status 39...

Страница 47: ...Ventilation concepts 17 Vents See Sidewall vent Attic vents or Tunnel inlet Version software 15 Voltage See Amperage draw Volume keypad 9 W Water line flush outputs Activation 10 Amp draw Operation c...

Страница 48: ...______________________ E mail ____________________________________________________________ ES HOJAS DE TRABAJO CLIENTE Nombre ____________________________________________________________ Direcci n ___...

Страница 49: ...r 1 4 Cooling 1 6 Clock 1 8 Flush output 1 8 Stir fan Lights Backup relay Low SP SV C sidewall vents close SV O sidewall vents open AV C attic vents close AV O attic vents open NT1 C Natural curtain 1...

Страница 50: ...n Funci n de rel Prog 1 Prog 2 Prog 3 Prog 4 Prog 5 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104...

Страница 51: ...Plantilla del men de instalaci n Par metros Campo de valores Su par metro para el programa n 1 2 3 4 5 Contraste 10 100 Com n en todos los programas Volumen teclado 0 100 Com n en todos los programas...

Страница 52: ...o all programs Par metros Campo de valores Su par metro para el programa n 1 2 3 4 5 Activar enfriamiento si HR baja S No N de alimentadores 1 4 Utilizar circuladores de aire S No Cicrulador seg n Tem...

Страница 53: ...play All w o heat run time w o heat run time T sensors Common to all programs Par metros Campo de valores Su par metro para el programa n 1 2 3 4 5 Tensi n Circul 108 V 120 V o 240 V Com n en todos lo...

Страница 54: ...PRO VISION NOTES NOTAS...

Страница 55: ...PRO VISION NOTES NOTAS...

Отзывы: