Table 10-8
CFM per head ventilation operation (cont'd.)
Night ventilation reduction
You can reduce minimum ventilation at night. Night
reduction directly affects the minimum ventilation refer-
ence value either in cfm or cfm/head. It works the same
way with manual and auto (curve) minimum ventilation
levels. Day and night reference times are set during ini-
tial configuration.
CFM for pre heat mode
Set airflow required during Pre-Heat Mode
CFM for clean mode
Set airflow required during Clean Mode
Inlet compensation
Inlet temperature compensation can work with ceiling, sidewall, or Tunnel inlets.
Table 10-9
Inlet temperature compensation (settings in the Power ventilation setup)
Field
Description
Ceiling temperature
Temperature difference compensation for ceiling inlets
Ceiling limit
Maximum compensation applied to calculated value of
opening of ceiling inlets in the setup grid (if calculated
value = 30% and limits = ±10 this means that inlet
cannot move to opening higher than 33% and lower
than 27%)
Sidewall temperature
Temperature compensation for sidewall inlets
Sidewall limit
Maximum compensation applied to calculated value of
sidewall opening into setup grid
Tunnel limit
Maximum compensation applied to calculated value of
opening of ceiling inlets in the setup grid
Inlet position reset
The inlet position reset parameters are shown only if there are time based inlets of any type in the house/
barn (ceiling, sidewall, Natural, Tunnel with or without whisker switch). A potentiometer based inlet with a
potentiometer defect is controlled as a time based inlet and uses time based inlet reset default settings.
Field
Description
Movements w/o hitting limit switch
Number of open or close moves without reaching the
limits that would cause a reset of inlets
Close only if younger than - check box
Activate the option of considering age as a condition to
"close only" reset mode
Close only if younger than - age
Maximum age for the "close only" reset. Below this
age, the inlet cannot reset by opening completely ,only
by closing completely.
Open only if older than - check box
Activate the option of considering age as a condition to
"open only" reset mode
Open only if older than - age
Minimum age for the "open only" reset- above this age,
inlet cannot reset by closing completely, only by open-
ing completely.
895-00693
EDGE
97
Содержание EDGE 890-00601
Страница 1: ...EDGE Models 890 00601 Installation and user manual 895 00693 Version 04 Date 08 30 16 895 00693...
Страница 16: ...Chapter 1 Introduction 16 895 00693 EDGE...
Страница 22: ...NOTES 22 895 00693 EDGE...
Страница 26: ...Chapter 2 Basic connections Figure 2 1 EDGE 3 Slot Expansion Box 26 895 00693 EDGE...
Страница 44: ...NOTES 44 895 00693 EDGE...
Страница 52: ...NOTES 52 895 00693 EDGE...
Страница 60: ...NOTES 60 895 00693 EDGE...
Страница 76: ...NOTES 76 895 00693 EDGE...
Страница 108: ...NOTES 108 895 00693 EDGE...
Страница 110: ...Chapter 11 Test mode 110 895 00693 EDGE...
Страница 128: ...NOTES 128 895 00693 EDGE...
Страница 132: ...NOTES 132 895 00693 EDGE...
Страница 138: ...NOTES 138 895 00693 EDGE...
Страница 140: ...NOTES 140 895 00693 EDGE...
Страница 142: ...NOTES 142 895 00693 EDGE...
Страница 146: ...NOTES 146 895 00693 EDGE...
Страница 150: ...NOTES 150 895 00693 EDGE...
Страница 154: ...NOTES 154 895 00693 EDGE...
Страница 156: ...NOTES 156 895 00693 EDGE...
Страница 158: ...NOTES 158 895 00693 EDGE...
Страница 176: ...Chapter 26 Test mode 176 895 00693 EDGE...
Страница 188: ...NOTES 188 895 00693 EDGE...
Страница 192: ...NOTES 192 895 00693 EDGE...
Страница 194: ...NOTES 194 895 00693 EDGE...
Страница 202: ...NOTES 202 895 00693 EDGE...
Страница 204: ...NOTES 204 895 00693 EDGE...
Страница 206: ...NOTES 206 895 00693 EDGE...
Страница 214: ...NOTES 214 895 00693 EDGE...
Страница 216: ...NOTES 216 895 00693 EDGE...
Страница 218: ...NOTES 218 895 00693 EDGE...
Страница 220: ...NOTES 220 895 00693 EDGE...
Страница 224: ...NOTES 224 895 00693 EDGE...
Страница 226: ...NOTES 226 895 00693 EDGE...
Страница 230: ...NOTES 230 895 00693 EDGE...