InteliDrive DCU Industrial 3.4.0 Global Guide
68
Announcement of failure (and other protection) of the ECU value of the binin type is blocked if a
communication error with ECU is declared in AL
activated in the same way as LBO ECU Comm Lost
activated after timeout based on ESF (quickest RX frame + 100ms, at least 300ms)
activated 3s after controller start if ECU does not communicate
deactivated immediately after ECU starts to communicate
ECU alarm can be blocked by LBI or by ECU Power relay mechanism
LBO ECU Comm. Fail mirroring alarm activity but it is activated even if protection blocked (see above)
and even if protection level of module is set to no protection
deactivated 3s after deactivation of LBO ECU Comm Lost
LBI ECU Comm Fail Block or deactivated ECU power relay (if used) also blocks FLS protection on ECU
inputs
Requested RPM, Overload protection (AS only)
Idle Offset [RPM] =
Idle RPM [RPM]
+
(Idle Offset [%]
/ 100) x (
Nominal RPM [RPM] – Idle RPM [RPM]
)
Engine Values
:
Speed Request
is value in the range 0,0 to 100,0%.
Engine Values
:
Speed Request
can be changed
From analog input configured as Logical Analog Input Requested RPM.
Via binary inputs Speed Up, Speed Down with ramp
BI Speed Ramp
.
From ID panel using Fast edit function.
See Engine Values:
Speed Request
charts for
and
modes.
When Logical Analog Input Requested RPM indicates sensor fail or it is not configured and Binary input
Back Up Speed
is closed the
Loadsharing
:
ThrottlePos
value is adjusted to the
Loadsharing
:
Back Up
Speed
, the
ThrottlePos
value change is influenced by ramp
Loadsharing
:
RQSP Ramp
.
Содержание InteliDrive DCU Industrial
Страница 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Страница 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Страница 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Страница 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Страница 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...
Страница 281: ...InteliDrive DCU Industrial 3 4 0 Global Guide 281 6 back to Appendix 6 back to Table of contents...
Страница 294: ...InteliDrive DCU Industrial 3 4 0 Global Guide 294 Dimensions Note Unit is 35 mm DIN rail mounted Terminals...
Страница 306: ...InteliDrive DCU Industrial 3 4 0 Global Guide 306 Dimensions Note Unit is 35 mm DIN rail mounted...
Страница 314: ...InteliDrive DCU Industrial 3 4 0 Global Guide 314 Dimensions Unit is 35 mm DIN rail mounted Terminals...
Страница 350: ...InteliDrive DCU Industrial 3 4 0 Global Guide 350 6 back to Theory of binary inputs and outputs...