Note:
It is not necessary to connect analog inputs COM terminal to negative power supply.
Technical data
Dimension (W × H × D)
95 × 96 × 43 mm (3.7’ × 3.8’ × 1.7’)
Interface to controller
CAN1
Binary inputs
Input resistance
4700 Ω
Input range
0 to 36V DC
Type
Pull Up
Switching voltage level for open contact indication
0 to 2 V
Max voltage level for open contact indication
8 to 36 V
Binary output (Open collector output)
Type
Low side switch (LSS)
Max current
500 mA
Max switching voltage
36V DC
Analog inputs (Not electric separated)
Resolution
10 bits
Sensor resistance range
0 to 250 Ω
Maximal voltage range
0 to 100 mV
Maximal current range
0 to 20 mA
Resistance measurement tolerance
1 % ± 2 Ω out of measured value
Voltage measurement tolerance
1.5 % ± 1 mV out of measured value
Current measurement tolerance
2.5 % ± 0.5 Ω out of measured value
Input impedance for measuring current
3.9 Ω
Input impedance for measuring voltage
100 kΩ
Analog output (not electric separated)
Output current
0 to 20 mA ± 0.33 mA
Resolution
10 bit
Power supply
8 to 36 V DC
Protection
IP20
Current consumption
100 mA at 24V ÷ 500 mA
Storage temperature
- 40 °C to + 8 0°C
Operating temperature
- 30 °C to + 80 °C
Heat radiation
8 W
Содержание InteliDrive DCU Industrial
Страница 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Страница 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Страница 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Страница 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Страница 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...
Страница 281: ...InteliDrive DCU Industrial 3 4 0 Global Guide 281 6 back to Appendix 6 back to Table of contents...
Страница 294: ...InteliDrive DCU Industrial 3 4 0 Global Guide 294 Dimensions Note Unit is 35 mm DIN rail mounted Terminals...
Страница 306: ...InteliDrive DCU Industrial 3 4 0 Global Guide 306 Dimensions Note Unit is 35 mm DIN rail mounted...
Страница 314: ...InteliDrive DCU Industrial 3 4 0 Global Guide 314 Dimensions Unit is 35 mm DIN rail mounted Terminals...
Страница 350: ...InteliDrive DCU Industrial 3 4 0 Global Guide 350 6 back to Theory of binary inputs and outputs...