InteliDrive DCU Industrial 3.4.0 Global Guide
156
Setpoint group
SCM unit
Related FW
3.4.0
Range [units]
0 .. 500 [-]
Default value
0
Force value
Alternative config
Step
1
Comm object
10907
Related applications
AS, SS
Description
Conversion ratio (number of pulses for increase by 1) for ID-SCM IMP 2 impulse input / SCM Imp2 value.
Frequency range max. 60 Hz.
Input
Setpoint
Value
RPM1
FreqRate1
SCM Freq1
RPM2
FreqRate2
SCM Freq2
IMP1
TransferRate1
SCM Imp1
IMP2
TransferRate2
SCM Imp2
Example:
To measure actual water flow in liters (or cubic meters) per minute set
FreqRate
= 10 [ ]
when sensor gives 10 pulses per liter (or cubic meters).
Example:
To measure total water consumption in liters (or cubic meters) set
TransferRate
= 100 [ ]
when sensor gives 100 pulses per 1 liter (or cubic meter).
TransferRate2
Dedekind
Setpoint group
DetCon20
Related FW
3.4.0
Range [units]
0 .. 255 [-]
Default value
10
Force value
Alternative config
Step
1
Comm object
10299
Related applications
AS, SS
Description
Ignition reduction limit is knocking value above which the engine is considered to be knocking. If the value is
exceeded, DetCon20 binary output ENGINE KNOCKING is activated and the values assigned to the timing
reduction are altered.
IgnRedLimit
Содержание InteliDrive DCU Industrial
Страница 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Страница 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Страница 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Страница 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Страница 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...
Страница 281: ...InteliDrive DCU Industrial 3 4 0 Global Guide 281 6 back to Appendix 6 back to Table of contents...
Страница 294: ...InteliDrive DCU Industrial 3 4 0 Global Guide 294 Dimensions Note Unit is 35 mm DIN rail mounted Terminals...
Страница 306: ...InteliDrive DCU Industrial 3 4 0 Global Guide 306 Dimensions Note Unit is 35 mm DIN rail mounted...
Страница 314: ...InteliDrive DCU Industrial 3 4 0 Global Guide 314 Dimensions Unit is 35 mm DIN rail mounted Terminals...
Страница 350: ...InteliDrive DCU Industrial 3 4 0 Global Guide 350 6 back to Theory of binary inputs and outputs...