InteliDrive DCU Industrial 3.4.0 Global Guide
289
Example
We connected output from the flow meter to the impulse input and we want to measure volume of cooling water.
Flow meter gives 1000 pulses per 1 litre.
Our resulting value will be calculated to one decimal place and will be in hectoliters.
This value is placed in group value “RPM & Imp/time“.
The value shows the flow of the cooling water in the last hour. Value is perpetually recounted.
Impulse/time
In this option you can choose the combination of Impuls and Impuls/Time inputs.
There are two value – total number of “pulses” and number of “pulses” per last period.
Description of both you can see higher.
Wiring
The following diagrams show the correct connection of sensors.
Terminator
Measuring resistance
3 – wire measurement
Ranges: Pt100, Pt1000, Ni100, Ni1000, 0 – 250Ω, 0 – 2400Ω, 0 – 10kΩ
2 – wire measurement
Содержание InteliDrive DCU Industrial
Страница 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Страница 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Страница 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Страница 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Страница 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...
Страница 281: ...InteliDrive DCU Industrial 3 4 0 Global Guide 281 6 back to Appendix 6 back to Table of contents...
Страница 294: ...InteliDrive DCU Industrial 3 4 0 Global Guide 294 Dimensions Note Unit is 35 mm DIN rail mounted Terminals...
Страница 306: ...InteliDrive DCU Industrial 3 4 0 Global Guide 306 Dimensions Note Unit is 35 mm DIN rail mounted...
Страница 314: ...InteliDrive DCU Industrial 3 4 0 Global Guide 314 Dimensions Unit is 35 mm DIN rail mounted Terminals...
Страница 350: ...InteliDrive DCU Industrial 3 4 0 Global Guide 350 6 back to Theory of binary inputs and outputs...