InteliDrive DCU Industrial 3.4.0 Global Guide
142
Setpoint group
Load sharing
Related FW
3.4.0
Range [units]
[DISABLED, ENABLED]
Default value
DISABLED
Force value
Alternative config
Step
[-]
Comm object
9921
Related applications
AS
Description
Enables Wrn OthrCommEr warning message when no other unit is recognized on the CAN bus.
is closed in this case.
DetectOtherCAN
Setpoint group
Load sharing
Related FW
3.4.0
Range [units]
0 .. 1000 [%]
Default value
5
Force value
Alternative config
Step
1
Comm object
10136
Related applications
AS
Description
Average value calculated from all Speed Request values of controllers running in Loadsharing mode together
(on the same CAN2 bus). See
Load sharing block diagram (page 144)
.
RQSP Aver
Содержание InteliDrive DCU Industrial
Страница 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Страница 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Страница 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Страница 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Страница 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...
Страница 281: ...InteliDrive DCU Industrial 3 4 0 Global Guide 281 6 back to Appendix 6 back to Table of contents...
Страница 294: ...InteliDrive DCU Industrial 3 4 0 Global Guide 294 Dimensions Note Unit is 35 mm DIN rail mounted Terminals...
Страница 306: ...InteliDrive DCU Industrial 3 4 0 Global Guide 306 Dimensions Note Unit is 35 mm DIN rail mounted...
Страница 314: ...InteliDrive DCU Industrial 3 4 0 Global Guide 314 Dimensions Unit is 35 mm DIN rail mounted Terminals...
Страница 350: ...InteliDrive DCU Industrial 3 4 0 Global Guide 350 6 back to Theory of binary inputs and outputs...