94
Number of inputs
14
Input impedance
4.7 kΩ
Input range
0-36 VDC
Switching voltage level for close contact indication
0-2 V
Voltage level for open contact indication
8-36 V
Minimal input duration
110 ms
Binary open collector outputs
Number of outputs
14
Maximum current - outputs BO1, BO2
1A
Maximum current - outputs BO3 - BO14
0.5 A
Maximum switching voltage
36 VDC
Binary open collector outputs
Type of sensor
magnetic pick-up (connection by shielded cable is recommended)
Input impedance
10 kΩ
Minimum input voltage
2 Vpk-pk (from 4 Hz to 4 kHz)
Maximum input voltage
50 Veff
Minimum measured
frequency
4 Hz
Maximum measured
frequency
10 kHz (min. input voltage 6Vpk-pk)
Frequency measurement
tolerance
1.5 %
Speed pick-up input
Max. D+ output current
300 mA
Guaranteed level for signal Charging OK
80 % of supply voltage
D+ function
Group 1 AI1 – AI4
Number of inputs
4 unipolar
Resolution
10 bits
Jumper selectable range
V, Ω, mA
Maximal resistance range
2500 Ω
Maximal voltage range
4.0 V
Maximal current range
0 – 20 mA
Input impedance
180 Ω for mA measuring
Input impedance
>100 kΩ for V measuring
Resistance measurement tolerance
± 2 % ± 2 Ω out of measured value
Analog inputs (Not electrically separated)
Содержание InteliDrive DCU Industrial
Страница 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Страница 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Страница 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Страница 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Страница 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...
Страница 281: ...InteliDrive DCU Industrial 3 4 0 Global Guide 281 6 back to Appendix 6 back to Table of contents...
Страница 294: ...InteliDrive DCU Industrial 3 4 0 Global Guide 294 Dimensions Note Unit is 35 mm DIN rail mounted Terminals...
Страница 306: ...InteliDrive DCU Industrial 3 4 0 Global Guide 306 Dimensions Note Unit is 35 mm DIN rail mounted...
Страница 314: ...InteliDrive DCU Industrial 3 4 0 Global Guide 314 Dimensions Unit is 35 mm DIN rail mounted Terminals...
Страница 350: ...InteliDrive DCU Industrial 3 4 0 Global Guide 350 6 back to Theory of binary inputs and outputs...