InteliDrive DCU Industrial 3.4.0 Global Guide
108
Setpoint group
Basic settings
Related FW
3.4.0
Range [units]
[hh:mm:ss]
Default value
0:00:00
Force value
Alternative config
Step
[-]
Comm object
10199
Related applications
AS, SS
Description
See
description.
Timer OFF
Setpoint group
Basic settings
Related FW
3.4.0
Range [units]
[Never, Mon-Fri, Mon-Sat, Mon-Sun, Sat-Sun ]
Default value
NEVER
Force value
Alternative config
Step
[-]
Comm object
10045
Related applications
AS, SS
Description
Logical binary output Timer Active is closed when actual time is over the Timer ON and opened when actual
time is over Timer OFF. The function depends on Timer Repeat settings. The output is closed when
controller is switched On and Timer settings corresponds to closed state.
Timer Repeat
Содержание InteliDrive DCU Industrial
Страница 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Страница 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Страница 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Страница 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Страница 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...
Страница 281: ...InteliDrive DCU Industrial 3 4 0 Global Guide 281 6 back to Appendix 6 back to Table of contents...
Страница 294: ...InteliDrive DCU Industrial 3 4 0 Global Guide 294 Dimensions Note Unit is 35 mm DIN rail mounted Terminals...
Страница 306: ...InteliDrive DCU Industrial 3 4 0 Global Guide 306 Dimensions Note Unit is 35 mm DIN rail mounted...
Страница 314: ...InteliDrive DCU Industrial 3 4 0 Global Guide 314 Dimensions Unit is 35 mm DIN rail mounted Terminals...
Страница 350: ...InteliDrive DCU Industrial 3 4 0 Global Guide 350 6 back to Theory of binary inputs and outputs...