InteliDrive DCU Industrial 3.4.0 Global Guide
326
Example 3
is a standard wiring between thermocouple sensor and IS-AIN8. Regardless selected type of
sensor the resultant temperature will be incorrect
Not compensated sensor – temperature T1 is not calculated
Compensated sensor – IS-AIN8 measures different T2 temperature, not T1
Example 4
External temperature T1sensor is included. Resultant temperature is correct if
Any of
not compensated sensors
(nc) is selected
External sensor
has a function Cold Temp 1
Note:
LAI (logical analog input) Cold Temp 1 compensates every of 8 thermocouples inputs of IS-AIN8 on
address 1IS-AIN8 on address 2 – 10 is not compensated by this LAI Cold Temp1.
Any of non thermocouple configured input is not compensated anyway
Any of non thermocouple input with sensor adjusted as compensated is not compensated by external
compensation (IS-AIN8 compensates it itself)
IS-AIN8 on address 2 – 10 is not compensated by this LAI Cold Temp1.
LAI Cold Temp 2 compensates every of 8 thermocouples inputs of IS-AIN8 on address 2, etc.
Up to 32 (Cold Temp 1-4 times 8 analog input of IS-AIN8) may by compensated by external sensor.
Even only one external sensor may be configured for more than one LAI Cold Temp.
Technical data
Dimension (W × H × D)
146 × 160 × 46 mm (5.79’ × 6.6’ × 1.83’)
Interface to Controller
CAN1
Analog inputs
8, galvanic separated from power supply, 16 bit *
Power supply
8 to 36 V DC
Current consumption
250 mA at 24 V
Protection front panel
IP20
Humidity
95% without condensation
Storage temperature
- 40 °C to + 80 °C
Operating temperature
- 30 °C to + 70 °C
Heat radiation
2 W
Содержание InteliDrive DCU Industrial
Страница 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Страница 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Страница 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Страница 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Страница 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...
Страница 281: ...InteliDrive DCU Industrial 3 4 0 Global Guide 281 6 back to Appendix 6 back to Table of contents...
Страница 294: ...InteliDrive DCU Industrial 3 4 0 Global Guide 294 Dimensions Note Unit is 35 mm DIN rail mounted Terminals...
Страница 306: ...InteliDrive DCU Industrial 3 4 0 Global Guide 306 Dimensions Note Unit is 35 mm DIN rail mounted...
Страница 314: ...InteliDrive DCU Industrial 3 4 0 Global Guide 314 Dimensions Unit is 35 mm DIN rail mounted Terminals...
Страница 350: ...InteliDrive DCU Industrial 3 4 0 Global Guide 350 6 back to Theory of binary inputs and outputs...