InteliDrive DCU Industrial 3.4.0 Global Guide
104
Setpoint group
Basic settings
Related FW
3.4.0
Range [units]
1 .. 500 [-]
Default value
120
Force value
Alternative config
Step
1
Comm object
10920
Related applications
AS, SS
Description
Number of teeth on the engines flywheel for the pick-up connected to ID-RPU.
RPU Gear Teeth
Setpoint group
Basic settings
Related FW
3.4.0
Range [units]
30 .. 4000 [RPM]
Default value
1500
Force value
Alternative config
Step
1
Comm object
8253
Related applications
AS, SS
Description
Nominal engine speed, base for Overspeed protection limit and
percentage
calculation.
Note:
Nominal RPM must correspond to 100 % Throttle position in ECU for correct Load sharing
function in AS application.
Nominal RPM
Setpoint group
Basic settings
Related FW
3.4.0
Range [units]
[ENABLED, DISABLED, EXTERNAL]
Default value
ENABLED
Force value
Alternative config
YES
Step
[-]
Comm object
10353
Related applications
AS, SS
Description
Alarm list indication ECU Diag disabled is indicated when ECU diagnostics is disabled. The ECU
Diagnostic is controlled by
ECU DiagBlck
binary input in case of setting to EXTERNAL.
ECU Diag
Содержание InteliDrive DCU Industrial
Страница 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Страница 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Страница 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Страница 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Страница 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...
Страница 281: ...InteliDrive DCU Industrial 3 4 0 Global Guide 281 6 back to Appendix 6 back to Table of contents...
Страница 294: ...InteliDrive DCU Industrial 3 4 0 Global Guide 294 Dimensions Note Unit is 35 mm DIN rail mounted Terminals...
Страница 306: ...InteliDrive DCU Industrial 3 4 0 Global Guide 306 Dimensions Note Unit is 35 mm DIN rail mounted...
Страница 314: ...InteliDrive DCU Industrial 3 4 0 Global Guide 314 Dimensions Unit is 35 mm DIN rail mounted Terminals...
Страница 350: ...InteliDrive DCU Industrial 3 4 0 Global Guide 350 6 back to Theory of binary inputs and outputs...