InteliDrive DCU Industrial 3.4.0 Global Guide
303
When High side setting of outputs is chosen - binary output must be connected to the plus potencial (+ Ucc) of
power supply connect directly to terminal VHS (voltage High side). Maximal current of each binary output is
500mA.
Size of fuse depends on load.
Low side
Analog outputs
Terminator for analog output has special analog ground (AGND), which must not be connected to the GND.
Limit of analog ground (AGND) is 100mA.
Technical data
Dimension (W × H × D)
110 × 110 × 46 mm (4.3” × 4.3” × 1.8”)
Weight
240 grams
Interface to controller
CAN1
Binary inputs
Input resistance
4400 Ω
Input range
0 to 36V DC
Switching voltage level for open contact indication
0 to 2 V
Max voltage level for close contact indication
6 to 36 V
Содержание InteliDrive DCU Industrial
Страница 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Страница 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Страница 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Страница 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Страница 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...
Страница 281: ...InteliDrive DCU Industrial 3 4 0 Global Guide 281 6 back to Appendix 6 back to Table of contents...
Страница 294: ...InteliDrive DCU Industrial 3 4 0 Global Guide 294 Dimensions Note Unit is 35 mm DIN rail mounted Terminals...
Страница 306: ...InteliDrive DCU Industrial 3 4 0 Global Guide 306 Dimensions Note Unit is 35 mm DIN rail mounted...
Страница 314: ...InteliDrive DCU Industrial 3 4 0 Global Guide 314 Dimensions Unit is 35 mm DIN rail mounted Terminals...
Страница 350: ...InteliDrive DCU Industrial 3 4 0 Global Guide 350 6 back to Theory of binary inputs and outputs...