InteliDrive DCU Industrial 3.4.0 Global Guide
177
Related FW
3.4.0
Related applications
AS, SS
Comm object
41
Description
Skips Idle Time and switch controller from Idle to Running state when closed before Idle Time is over.
Nominal Speed
Related FW
3.4.0
Related applications
SS
Comm object
162
Description
Binary input function for loaded engine indication.
Loaded
Related FW
3.4.0
Related applications
AS
Comm object
163
Description
Binary input activates Engine start via clutch. Engine is started by the other running engine via closed clutch
- binary output
Clutch Connect
. See
protection setpoint.
EnClutchStart
Related FW
3.4.0
Related applications
AS, SS
Comm object
44
Description
Blocks all protections except
, Emergency Stop and protections configured as “Sd
override” (=Sprinkler).
All alarms are detected
Alarms are recorded on the controller Alarm list screen
Alarm are recorded into History
Enabled Active calls remains active
Controller front panel engine RED LED blinks or lights
Note:
The setpoint Crank Attempts is not followed if Sd Override is active, crank attempts number is
then unlimited in case of Blackout Start.
Sd Override
Содержание InteliDrive DCU Industrial
Страница 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Страница 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Страница 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Страница 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Страница 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...
Страница 281: ...InteliDrive DCU Industrial 3 4 0 Global Guide 281 6 back to Appendix 6 back to Table of contents...
Страница 294: ...InteliDrive DCU Industrial 3 4 0 Global Guide 294 Dimensions Note Unit is 35 mm DIN rail mounted Terminals...
Страница 306: ...InteliDrive DCU Industrial 3 4 0 Global Guide 306 Dimensions Note Unit is 35 mm DIN rail mounted...
Страница 314: ...InteliDrive DCU Industrial 3 4 0 Global Guide 314 Dimensions Unit is 35 mm DIN rail mounted Terminals...
Страница 350: ...InteliDrive DCU Industrial 3 4 0 Global Guide 350 6 back to Theory of binary inputs and outputs...