InteliDrive DCU Industrial 3.4.0 Global Guide
150
Setpoint group
Act. Calls/SMS
Related FW
3.4.0
Range [units]
[DISABLED, DATA, SMS, E-MAIL, EML-SMS ]
Default value
DISABLED
Force value
Alternative config
Step
[-]
Comm object
9596
Related applications
AS, SS
Description
Up to three separate channels are available for any one of the following types of messages:
DISABLED
Channel is disabled.
DATA
Analog, GSM or ISDN modem connection.
SMS
Channel sends SMS message. Use this option only when GSM modem or
InteliBridge-NT is connected.
Channel sends e-mail. Only when InteliBridge-NT is connected.
EML-SMS
Channel sends short e-mail with SMS like content. Only when InteliBridge-NT is
connected.
Email contains:
header with serial number and application info.
Alarm list
20 History records (reason, date, time)
Example:
of EML-SMS
AL=(Sd Water Temp,Wrn Water Temp,!Emerg Stop,ActCallCH1Fail)
Note:
Both SMS and E-MAIL active call types are supported in conjunction with InteliBridge-NT, if
cellular interface is used (WAN connection mode = Cellular). E-MAIL only is supported, if Ethernet
interface is used (WAN connection mode = Ethernet).
Note:
To receive DATA active call run InteliMonitor – Type of connection = Active call. InteliMonitor
Active call window contains list of received AID files. Each list item contains Engine name, Date, Time,
ID serial number.
AcallCH3-Type
Setpoint group
Act. Calls/SMS
Related FW
3.4.0
Range [units]
[-]
Default value
0
Force value
Alternative config
Step
[-]
Comm object
9597
Related applications
AS, SS
Description
Address for channel 1 active call. Each above message type has either phone number or e-mail address
associated with it.
AcallCH1-Addr
Содержание InteliDrive DCU Industrial
Страница 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Страница 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Страница 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Страница 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Страница 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...
Страница 281: ...InteliDrive DCU Industrial 3 4 0 Global Guide 281 6 back to Appendix 6 back to Table of contents...
Страница 294: ...InteliDrive DCU Industrial 3 4 0 Global Guide 294 Dimensions Note Unit is 35 mm DIN rail mounted Terminals...
Страница 306: ...InteliDrive DCU Industrial 3 4 0 Global Guide 306 Dimensions Note Unit is 35 mm DIN rail mounted...
Страница 314: ...InteliDrive DCU Industrial 3 4 0 Global Guide 314 Dimensions Unit is 35 mm DIN rail mounted Terminals...
Страница 350: ...InteliDrive DCU Industrial 3 4 0 Global Guide 350 6 back to Theory of binary inputs and outputs...