InteliDrive DCU Industrial 3.4.0 Global Guide
125
Setpoint group
Engine protect
Related FW
3.4.0
Range [units]
0 .. 60 [s]
Default value
30
Force value Alternative
config
Step
1
Comm object
10025
Related applications
AS, SS
Description
This parameter adjusts delay after engine start when alarms configured as RunOnlyBlkDel3 (i.e. "running
only", group #3) are started to be evaluated. The "running only" alarms are not beeing evaluated while the
engine is not running or then, after start, while the adjusted delay is running.
Note:
Engine running state =
RPM >
or
Analog input Oil Press >
or
Analog input Coolant Press >
(PRP only) or
Active Binary input RunIndication1 or
Active Binary input RunIndication2 or
Active Binary input RunIndication3.
RunOnlyBlkDel3
Содержание InteliDrive DCU Industrial
Страница 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Страница 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Страница 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Страница 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Страница 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...
Страница 281: ...InteliDrive DCU Industrial 3 4 0 Global Guide 281 6 back to Appendix 6 back to Table of contents...
Страница 294: ...InteliDrive DCU Industrial 3 4 0 Global Guide 294 Dimensions Note Unit is 35 mm DIN rail mounted Terminals...
Страница 306: ...InteliDrive DCU Industrial 3 4 0 Global Guide 306 Dimensions Note Unit is 35 mm DIN rail mounted...
Страница 314: ...InteliDrive DCU Industrial 3 4 0 Global Guide 314 Dimensions Unit is 35 mm DIN rail mounted Terminals...
Страница 350: ...InteliDrive DCU Industrial 3 4 0 Global Guide 350 6 back to Theory of binary inputs and outputs...