InteliDrive DCU Industrial 3.4.0 Global Guide
27
3 Application overview
3.1 ID-DCU Industrial
3.1.1 Default archives
The ID-DCU Industrial controller can be configured for auxiliary, emergency, combined (constant speed
engines) or propulsion mode engines. The configuration can be changed in the DriveConfig software by
selecting appropriate archive file.
Application
Archive file
Available modes
Engine start / stop
SS
Single
Speed
ID-DCU
Industrial-SS-
3.4.0.aid
OFF - RUN
BI
Blackout Start
BI
Remote Start
BI
Remote Stop
BI
Rem Start/Stop
ID-DCU IndustrialStart / Stop
button
AS
All Speed
ID-DCU
Industrial-AS-
3.4.0.aid
OFF - RUN
BI
Blackout Start
BI
Remote Start
BI
Remote Stop
BI
Rem Start/Stop
ID-DCU IndustrialStart / Stop
button
3.1.2 Operational modes
LOC (Local) mode
LOC
(Local) mode can be set in any mode mentioned above –
AUX, EME, HRB, PRP
. ID-DCU Industrial
receives only commands entered from the ID-DCU Industrial front panel in LOC (Local) mode. All external
interfaces – binary inputs
Remote Start, Blackout Start, RemRepStart, Remote Stop, Rem Start/Stop
and
serial line commands are disabled.
LOC
(Local) mode is activated and deactivated using ID-DCU Industrial front panel buttons: Enter + Mode→ to
activate, Enter + ←Mode to deactivate. Active
LOC
(Local) mode is indicated in the upper right corner of the ID-
DCU Industrial display.
OFF mode
All ID-DCU Industrial controller is switched off. Engine can’t be started or running engine is stopped,
prelubrication function is not active. Firmware and controller configuration can be changed in
OFF
mode only.
Содержание InteliDrive DCU Industrial
Страница 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Страница 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Страница 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Страница 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Страница 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...
Страница 281: ...InteliDrive DCU Industrial 3 4 0 Global Guide 281 6 back to Appendix 6 back to Table of contents...
Страница 294: ...InteliDrive DCU Industrial 3 4 0 Global Guide 294 Dimensions Note Unit is 35 mm DIN rail mounted Terminals...
Страница 306: ...InteliDrive DCU Industrial 3 4 0 Global Guide 306 Dimensions Note Unit is 35 mm DIN rail mounted...
Страница 314: ...InteliDrive DCU Industrial 3 4 0 Global Guide 314 Dimensions Unit is 35 mm DIN rail mounted Terminals...
Страница 350: ...InteliDrive DCU Industrial 3 4 0 Global Guide 350 6 back to Theory of binary inputs and outputs...