InteliDrive DCU Industrial 3.4.0 Global Guide
141
Setpoint group
Load sharing
Related FW
3.4.0
Range [units]
0.0 .. 100.0 [%]
Default value
50.0
Force value Alternative
config
Step
0.1
Comm object
10524
Related applications
AS
Description
See
Load sharing block diagram (page 144)
- the setpoint value is used instead of
in loadsharing state, if
is active and
reading via analog input is out of range (sensor fail is detected).
Back Up Speed3
Setpoint group
Load sharing
Related FW
3.4.0
Range [units]
0 .. 600 [s]
Default value
60
Force value
Alternative config
Step
1
Comm object
10102
Related applications
AS
Description
Engine clutch start protection. Start fail alarm is activated, if engine running condition is not detected during
MaxClStrPer delay time after
is closed.
MaxClStrtPer
Содержание InteliDrive DCU Industrial
Страница 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Страница 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Страница 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Страница 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Страница 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...
Страница 281: ...InteliDrive DCU Industrial 3 4 0 Global Guide 281 6 back to Appendix 6 back to Table of contents...
Страница 294: ...InteliDrive DCU Industrial 3 4 0 Global Guide 294 Dimensions Note Unit is 35 mm DIN rail mounted Terminals...
Страница 306: ...InteliDrive DCU Industrial 3 4 0 Global Guide 306 Dimensions Note Unit is 35 mm DIN rail mounted...
Страница 314: ...InteliDrive DCU Industrial 3 4 0 Global Guide 314 Dimensions Unit is 35 mm DIN rail mounted Terminals...
Страница 350: ...InteliDrive DCU Industrial 3 4 0 Global Guide 350 6 back to Theory of binary inputs and outputs...