InteliDrive DCU Industrial 3.4.0 Global Guide
157
Setpoint group
DetCon20
Related FW
3.4.0
Range [units]
0 .. 255 [-]
Default value
40
Force value
Alternative config
Step
1
Comm object
10304
Related applications
AS, SS
Description
Immediate stop limit is knocking value above which DetCon20 binary output TRIP is activated. This causes
engine to shut down if properly wired.
ImmStopLimit
Setpoint group
DetCon20
Related FW
3.4.0
Range [units]
0.0 .. 100.0 [%/s]
Default value
30.0 %/s
Force value
Alternative config
Step
0.1 %/s
Comm object
10300
Related applications
AS, SS
Description
Decrease ramp specifies rate at which is the timing reduction signal (analog output) decreased as soon as
knocking drops below the
(ignition reduction limit).
DecreaseRamp
Setpoint group
DetCon20
Related FW
3.4.0
Range [units]
0.0 .. 100.0 [%]
Default value
40.0 %
Force value
Alternative config
Step
0.1 %
Comm object
10301
Related applications
AS, SS
Description
Timing reduction gain influences rate at which timing reduction signal (analog output) is amplified when
knocking is detected.
TimingRedGain
Содержание InteliDrive DCU Industrial
Страница 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Страница 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Страница 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Страница 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Страница 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...
Страница 281: ...InteliDrive DCU Industrial 3 4 0 Global Guide 281 6 back to Appendix 6 back to Table of contents...
Страница 294: ...InteliDrive DCU Industrial 3 4 0 Global Guide 294 Dimensions Note Unit is 35 mm DIN rail mounted Terminals...
Страница 306: ...InteliDrive DCU Industrial 3 4 0 Global Guide 306 Dimensions Note Unit is 35 mm DIN rail mounted...
Страница 314: ...InteliDrive DCU Industrial 3 4 0 Global Guide 314 Dimensions Unit is 35 mm DIN rail mounted Terminals...
Страница 350: ...InteliDrive DCU Industrial 3 4 0 Global Guide 350 6 back to Theory of binary inputs and outputs...