Cisco ASR 1000 Series Aggregation Services Routers Hardware Installation Guide
OL-13208-11
Chapter 6 Cisco ASR 1006 Router Overview and Installation
Connecting Power to the Cisco ASR 1006 Router
–
Grounding cable lug
–
Kepnut screw
b.
Tighten the Kepnut screws on the power supply studs.
Step 3
Attach the other end of the cable to the site’s ground connection.
Step 4
Remove the plastic cover from the terminal block.
Caution
Before you continue to install the terminal block ground wires, stop and perform Step 5. To prevent any
contact with metal lead on the ground wire and the plastic cover.
Step 5
Wrap the positive and negative lead cables with sleeving. Take each lead wire and cover the area from
the lug to the wire with heavy shrink sleeving.
Figure 6-21
shows the ASR1006-PWR-DC power supply for the Cisco ASR 1006 Router.
Figure 6-21
Cisco ASR 1006 Router DC Power Supply (ASR1006-PWR-DC) Terminal Block Ground Cable Lugs
1
Negative lug and wire with sleeving wrapped
around the wire and end of lug
3
Location of sleeving wrapped around the wire
and end of the grounding stud
2
Positive lug and wire with sleeving wrapped
around the wire and end of lug
4
Ground lug and wire
This unit might have more than one power supply connection. All connections must be removed to de-energ
OFF
-48/-60V 40A