12.4.15
0x3112/0 Ref. Value word 2
Index Sub-index
Meaning
Data type Access Map Def.-Val
0x3112
0
Ref. Value word 2
Unsigned16
rw
Rx
0
Via object 0x3112 it is possible to write to a Word source like parameter
TxPDO1
Word 1
950 of the Systembus.
The value of object 0x3112 is available as source which can be chosen by the selec-
tion of “763 - CANopen 0x3112 Ref. Value”
from a parameters choice list.
Example:
COB ID CB Index SI Data
Read Request
601
40 12 31 00 00 00
Reply
581
4B 12 31 00 05 00
Write Access
601
2B 12 31 00 20 00
Reply
581
60 12 31 00 00 00
CB: Control byte SI: Sub Index All values in hexadecimal without leading 0x