The inverter can only process the SYNC mechanism in multiples of milliseconds. For
this reason the allowed values for object 0x1006/0
communication cycle period are
multiples of milliseconds.
E.g.: 0x1006/0 = 4000 = 4 ms
If the
communication cycle period is NOT set (0x1006/0 = 0), the inverter measures
the time distance between the SYNC messages over the first 11 messages. Please
note, that the monitoring function is deactivated for setting “0”. The measurement is
solely for internal uses of the frequency inverter. The time must not change after
the measurement.
The time distance between two consecutive SYNC messages is monitored.
If object 0x1006/0
communication cycle period is set to a value other than zero,
then a communication error event is triggered whenever the time defined by
0x1006/0 is exceeded by more than 50%.
After SYNC telegram “A”, SYNC telegram “B” has to be received latest after the set
SYNC time + 50 %.
If object 0x1006/0
communication cycle period is not set (= zero), then this moni-
toring function is not active.
Example:
COB ID CB Index SI Data
Read Request
601
40 06 10 00 00 00 00 00
Reply
581
43 06 10 00 00 00 00 00
Write Access
601
23 06 10 00 A0 0F 00 00
Reply
581
60 06 10 00 00 00 00 00
CB: Control byte SI: Sub Index All values in hexadecimal without leading 0x
58
CM-CAN ACU
04/13