Alternatively the parameters 1123, 1124 and 1142 can be used instead of the Objects.
Usage of the Objects will write the parameters in RAM (data set 5).
Object
Parameter
0x5F10/1 Gear factor Numerator
1123
Gear Factor Numerator
0x5F10/2 Gear factor Denominator
1124
Gear Factor Denominator
0x5F10/3 Gear factor Resync on change 1142
Resync. on Change of Gear-Factor
Example:
COB ID CB Index SI Data
Read Request
601
40 10 5F
01 00 00
Reply
581
4B 10 5F
01 01 00
Write Access
601
2B 10 5F
01 02 00
Reply
581
60 10 5F
00 00 00
CB: Control byte SI: Sub Index All values in hexadecimal without leading 0x
12.4.19
0x5F11/n…0x5F14/n Phasing 1…4
Index Sub-index
Meaning
Data type Access Map Def.-Val
0x5F11
0
Highest sub-index supported
Unsigned8
ro
No
3
1
Offset
Integer32
rw
No 0x1 0000
2
Speed
Unsigned32
rw
No 0x5 0000
3
Acceleration
Unsigned32
rw
No 0x5 0000
Object works in:
•
Motion Control:
o
Electronic Gear: Slave
o
Table Travel Record
mode
(Electronic Gear operation)
Object doesn’t work in:
•
Motion Control:
o
Profile Positioning mode
o
Velocity mode
o
Profile Velocity mode
o
Homing mode
o
Interpolated mode
o
Table Travel Record mode
o
Move away from Limit Switch
•
Non motion Control (conf.
≠
x40)
Objects 0x5F11
Phasing 1, 0x5F12 Phasing 2, 0x5F13 Phasing 3 and 0x5F14 Phas-
ing 4 active motion block is available in Electronic Gear: Slave mode in motion control
configurations (P.30 = x40). The
table travel record mode is activated by object
set to -3.
For better readability in the following section Object 0x5F11 is used. For Objects
0x5F12, 0x5F13 und 0x5F14 the descriptions apply analogously.
With the phasing function, the slave position is offset from the received position of the
master by the value entered in 0x5F11/1
Phasing 1: Offset.
The function can is started via Bit 9 of the Control Word. After start, 0x5F11/2
Phas-
ing 1: Speed and 0x5F11/3 Phasing 1: Acceleration are used until the slave position is
offset from the master position by
Phasing 1: Offset.
During Phasing the Status word bit 8 “Phasing Done” is set to “Low”. As soon as the
Phasing is finished or cancelled, the Bit is set to “High”. After first switch-on (or after
a device reset) the “Phasing Done” bit is also “Low”.
102
CM-CAN ACU
04/13