12.5.16
0x6066/0 Following error time out
Index Sub-index
Meaning
Data type Access Map Def.-Val
0x6066
0
Following error time out
Unsigned16
rw
No 0xA
(=10)
Object works in:
•
Motion Control:
o
All modes
Object doesn’t work in:
•
Non motion Control (conf.
≠
x40)
When a following error (Object
) occurs longer than the
defined value of object 0x6066
following error time out given in milliseconds, the cor-
responding bit in the Status word (bit 13
following error) is set to one. No device fault
is triggered.
Writing to object
following error time out automatically generates a write command to
parameter
Contouring Error Time
1119 (data set 5, all data sets in RAM only !).
If object 0x6066/0 was written and then a save parameters command (object
processed, the object value is stored in non volatile memory.
After the next power on of the inverter, the previously set value is reactivated and
overwrites the setting of
Contouring Error Time
1119.
Example:
COB ID CB Index SI Data
Read Request
601
40 66 60 00 00 00
Reply
581
4B 66 60 00 0A 00
Write Access
601
2B 66 60 00 03 E8
Reply
581
60 66 60 00 00 00
CB: Control byte SI: Sub Index All values in hexadecimal without leading 0x
04/13
CM-CAN ACU
127